40037
Sys Power
System Power (Read Only) is the Nominal system power based on
the values of Nominal system volts and Nominal system current.
40041
Word Order
Word Order controls the order in which the
receives
or sends floating - point numbers:- normal or reversed register
order.In normal mode, the two registers that make up a floating
point numbers are sent most significant bytes first.
In reversed register mode , the two registers that make up
a floating point numbers are sent least significant bytes first.
To set the mode, write the value ‘2141.0’ into this register-
the instrument will detect the order used to send this value and
set that order for all ModBus transaction involving floating point
numbers.
instrument
This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on the per
phase 666.6MVA Restriction of power combined with PT primary
40035
CT Pimary
40039
40031
Analog Out 2-
Para Set
This address is used to set the parameter for Analog Output 2..
Write one of the parameter no. As per the options given in
Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.
40033
PT Primary
This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV L-L
depends on the per phase 666.6MVA Restriction of power
combined with CT primary
50
This address is used to set
Energy on Rs485 is in Wh rollover count can be from 7 to 14.
If it is in KWh then rollover count can be from 7 to 12 & for MWh
rollover count can be from 7 to 9.
the rollover count for energy. If
Energy digit
Reset Count