090317-NUT-SPLIT-MULTISPLIT-EN
14/24
EN
•
Override (MANUAL / AUTO COOL)
If the remote control is out of order or lost, the user can operate the product manually by using the override button:
- On ducted, cassette, floor/ceiling or console products, this button is located on the indoor unit display panel
(m-F-O-3); it is labelled "MANUAL":
- On wall-mounted products, it is located on the electrical connection box, it is accessed by lifting up the front
panel, and it is labelled "AUTO COOL":
- Using the override button:
- Press once: the product will start in automatic (AUTO) mode, the operational indicator
"OPERATION" will be displayed; the remote control can now be used.
- Press a second time: the product starts in cooling (COOL) mode and high speed fan mode, the
operational indicator "OPERATION" flashes, the remote control cannot be used. After 30 minutes of
operating in cooling mode, the product switches to automatic "AUTO" mode.
- Press a third time: the product stops, the operational indicator "OPERATION" is switched off, the
remote control can now be used.
4- DISPLAY
•
Display PCB (Cassettes and duct products)
It is located on the front of the indoor unit (cassette model) or on the front of the display box (DUCT model).
I
= Receiver
m
= Manual operation button (override)
n
= Operational indicator "OPERATION"
o
= Programming indicator "TIMER"
p
= Hot start or "PRE-DEF" indicator (heating mode)
q
= Operating fault indicator "ALARM"