Discovering the origin of the problem
1. Open control board and
check if it has 230V power
supply
2. Check input fuses
3. Disconnect the motor from
control board and test them
by connecting directly to
power supply in order to find
out if they have problems.
4. If the motor works, the pro
-
blem is on the control board.
Pull it out and send it to our
ZERO technical services for
diagnosis.
5. If the motor doesn’t work,
remove them from installation
site and send to our ZERO te-
chnical services for diagnosis.
Check all motion axis and associated motion systems related with the motor and the gate to find out what is the problem.
1. Check capacitors, testing
operator with new capacitors;
2. If capacitors are not the
problem, disconnect motors
from control board and test
them by connecting directly to
power supply in order to find
out if they have problems.
3. If the motors work, the pro
-
blem is from control board.
Pull it out and send it to our
ZERO technical services for
diagnosis;
4. If the motors doesn’t work,
remove them from installation
site and send to our ZERO te-
chnical services for diagnosis
All ZERO control boards have LEDs that easily allow to conclude which devices are with anomalies. All safety devices LEDs
(DS) in normal situations remain On. All “START” circuits LEDs in normal situations remain Off.
If LEDs devices are not all On, there is some security systems malfunction (photocells, safety edges), etc.
1 • Close with a shunt all safety systems on the control board (check manual of the control board in question). If the automa
-
ted system starts working normally check for the problematic device.
2 • Remove one shunt at a time until you find the malfunction device .
3 • Replace it for a functional device and check if the motor works correctly with all the other devices. If you find another one
defective, follow the same steps until you find all the problems.
If “START” circuits LEDs are turn On, there is a control device sending permanent signal.
1 • Disconnect all wires from START terminal input (terminal 3).
2 • If the LED turned Off, try reconnecting one device at a time until you find the defective device.
In case described procedures fell, remove control board and sendto our technical services for diagnosis.
Check all motion axis and associated motion systems related with the motor and the gate to find out what is the problem.
1. Check capacitors, testing
with new capacitors;
2. If capacitors are not the
problem, disconnect motor
from control board and test
it by connecting directly to
power supply in order to find
out if it is broken;
3. If the motor doesn’t work,
remove it from installation
site and send to our ZERO te-
chnical services for diagnosis.
4. If motor work well and
move gate at full force during
the entire course, the pro
-
blem is from controller. Set
force using trimmer on the
board. Make a new working
time programming, giving
suffient time for opening and
closing with appropriate force.
5. If this doesn’t work, remo
-
ve control unit and send it to
ZERO technical services servi-
ces.
NOTE: Setting force of the controller should be sufficient to make the gate open and close without stopping, but should stop
and invert with a little effort from a person. In case of safety systems failure, the gate shall never cause physical damaged to
obstacles (vehicles, people, etc.).