ZCOM230|CONTROL PANEL | COMANDO 230V
PROGRAMMING THE WORKING TIME AND ENGINE’S PAUSE
STEP 1
With the gate closed, place the DIP 9 to “ON”, press transmit-
ter (already programmed) / START and the gate will start to
open.
STEP 2
When the gate stops at the open position (opening limit-swi
-
tch is enabled), wait for the desired pause time (*) and give
a new START to close. This waited time represents the time
that the engine will PAUSE between the end of the opening
maneuver and the automatic closure’s start. This automatic
closure will only happen if the DIP 4 and 5 are in the selected
positions to activate it. If during the working time setting you
would like to activate the automatic closing after photocells
interruption (3 seconds) just interrupt the photocells signal
during pause counting time.
STEP 3
When the gate reaches the closed position, change the DIP 9
to OFF to finish programming and CODE LED will blink and go
off. If the DIP SWITCH is leaved ON, the programming won’t
be finalized.
PROGRAMMING THE PEDESTRIAN WORK TIME
STEP1
With the gate in closed mode put the DIP 9 to ON.
STEP2
Press the button nº2 to start opening the gate. Upon reaching
the desired position press again the button to stop the engi
-
ne. Wait the desired pause time and give a new START to clo
-
se. This waited time represents the time that the engine will
wait between the end of the pedestrian’s opening maneuver
and the automatic closure’s start. Nearing the limit-switch’s
end, the engine will stop.
STEP 3
The setting is completed, place the DIP 9 to OFF to finalize and
close the pedestrian programming.
FORCE AND SENSITIVITY REGULATION (ANTI-CRUSHING)
The control board has 2 trimmers (rotary knobs):
RV1 - Allows the engine sensitivity regulation (increases sensiti
-
vity by rotating it in the clockwise direction);
RV2 - Allows the engine power regulation (increases the force
by rotating in the clockwise direction );
Warning: To use anti-crush function (recommended for small
gates), it is necessary to regulate first the engine’s power with
the trimmer RV2 and right after the sensitivity with trimmer
RV1. If you change the engine’s power after performing a Wor
-
king Time and Engine Pause programming , a new one is going
to be needed.
ILUMINATED LIGHTBULB IN PAUSE TIME
(10 AND 11 TERMINALS)
01 • If you wish to activate this function, when programming
work time and engine’s pause at the point 2, do the following
operation from (*):
•Press the pedestrian transmitter button while the gate is pau
-
sed, between the opening and closing.
NOTE: In case of using the 11 and 12 terminals for the lightbulb,
the DIP3 must be OFF and the Lightbulb must have a circuit bo
-
ard to make the lamp to blink.
PROGRAMMING SAFETY EDGS FUNCTION (terminal 6)
The control panel could accept wire safety edges and 8.2 Ohm
resistive edges.
During programming working time the panel recognize by itself
the type of safety edge installed.
Factory set on wire edge, whit shunt placed on terminal 6 and
terminal 7.
if you have to change to 8.2 KOhm firstly make the transmitter
programming and then remove the shunt and place the edge’s
connection.
NOTE: if LED CODE signal flashing once you powered the control
panel it means that the safety edge is wrongly configured.
RESET TO FACTORY DEFAULTS
If the control board blocks and a RESET is needed, follow these
steps:
- Put DIP 9 to ON position
- Power off the control unit by removing the M1 connectors
plug, affter few secons power on.
- Put DIP 9 to OFF position.