TMD-Display View
http://www.zennio.com
Technical Support:
http://support.zennio.com
83
1 Bit
I/O
C T R W -
DPT_Switch
0/1
[Pn] [X2] Two Objects - Long Press: "1"
1-bit Generic Control
1 Bit
I/O
C T R W -
DPT_Switch
0/1
[Pn] [X2] Two Objects - Long Press: "0/1"
1-bit Generic Control
1 Byte
I/O
C T R W -
DPT_Value_1_Ucount
0 - 255
[Pn] [X2] Enumeration
Rotating value change
1 Byte
I/O
C T R W -
DPT_Value_1_Ucount
0 - 255
[Pn] [X2] Two Objects - Long Press: (1-
byte)
Send selected 1-byte value on long
press
29, 42, 55, 68,
81, 94, 107, 120
133, 146, 159,
172, 185, 198,
211, 224
1 Bit
I
C - - W -
DPT_Switch
0/1
[Pn] [X2] LED On/Off
0 = On; 1 = Off
1 Bit
I
C - - W -
DPT_Switch
0/1
[Pn] [X2] LED On/Off
0 = Off; 1 = On
225
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
226
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Temperature Source 1
External Sensor Temperature
227
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Temperature Source 2
External Sensor Temperature
228
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Effective Temperature
Effective Control Temperature
229
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[T1] Special Mode
1-byte HVAC Mode
230
1 Bit
I
C - - W -
DPT_Ack
0/1
[T1] Special Mode: Comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: Comfort
0 = Off; 1 = On
231
1 Bit
I
C - - W -
DPT_Ack
0/1
[T1] Special Mode: Standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: Standby
0 = Off; 1 = On
232
1 Bit
I
C - - W -
DPT_Ack
0/1
[T1] Special Mode: Economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: Economy
0 = Off; 1 = On
233
1 Bit
I
C - - W -
DPT_Ack
0/1
[T1] Special Mode: Protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[T1] Special Mode: Protection
0 = Off; 1 = On
234
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[T1] Window Status (Input)
0 = Closed; 1 = Open
235
1 Bit
I
C - - W -
DPT_Ack
0/1
[T1] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
236
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[T1] Special Mode Status
1-byte HVAC Mode
237
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Basic Setpoint
Reference Setpoint
238
1 Bit
I
C - - W -
DPT_Step
0/1
[T1] Setpoint Step
0 = -0.5ºC; 1 = +0.5ºC
239
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 -
670760.00
[T1] Setpoint Offset
Float Offset Value
240
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Setpoint Status
Current Setpoint
241
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00 [T1] Basic Setpoint Status
Current Basic Setpoint
242
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 -
670760.00
[T1] Setpoint Offset Status
Current Setpoint Offset
243
1 Bit
I
C - - W -
DPT_Reset
0/1
[T1] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[T1] Offset Reset
Reset offset