TMD-Display View
TMD-Display View
http://www.zennio.com
Technical Support:
http://support.zennio.com
58
communication objects, where “Xj” depends on the button (A1, A2, B1, etc.) and “Pn”
depends on the page number.
Switch
Figure 40
Individual Button - Switch.
Action
: sets the value to be sent to the bus (through object “
[Pn] [Xj]
Switch
“) when the user touches the button. The options are “Send 0”, “Send
1
” and “Toggle 0/1”.
Text for ‘0’
and
Text for ‘1’
: sets the text to be displayed between the icons
o
f the buttons when the values ‘0’ and ‘1’ are sent, respectively.
LED illumination control
: sets the behaviour of the LEDs on the buttons.
The options are “Regular”, “State-dependent” and “Dedicated Object”.
In case of selecting the latter, the object “
[Pn] [Xj] LED On/Off
” will be
included in the project topology (the desired values to turn on or turn off the
LED are set by the parameter
Object Value
).
Two Objects (Short Press / Long Press)
Action on Short press
: sets the value to be sent to the bus
(through “
[Pn]
[Xj] Two switches - Short press
”) when the user short-presses the button.
The options are “Send 0”, “Send 1”, “Toggle 0/1” and “Send 1-byte Unsigned
Int Value
”. In case of selecting the latter, an additional parameter (“
Value
”)
will be displayed to enter the desired one-byte value (0 - 255).
Text for ‘0’
and
Text for ‘1’
: sets the text to be displayed between the
icons of the buttons when the values ‘0’ and ‘1’ are sent, respectively.