KLIC-MITT v2
Technical Support:
26
Auto
: if the automatic flap position control is available,
1 / 2 / 3 / 4 / 5
: or any of the available flap positions.
Setpoint
[
disabled
/enabled
]:
Value:
o
No Change
: the last setpoint temperature value will kept. Only
available if
Setpoint
parameter remains disabled.
o
16…
25
…31
ºC
: concrete value of the set temperature.
2.2.6
ERROR HANDLING
KLIC-MITT v2 is capable of managing two error types that do not entail any previous
parameter configuration:
Communication (or internal) errors
: errors in the communication process
between KLIC-MITT v2 and the A/C unit. These types of errors are notified by
the green LED as indicated below:
Communication error
: KLIC-MITT v2 is not able to establish
communication with the A/C machine. The green LED remains on.
No response
(time out)
: KLIC-MITT v2 received no response after
sending a request to the A/C unit. The green LED blinks twice and stays
off during 3 seconds.
Wrong acknowledgement
: KLIC-MITT v2 received an unexpected
response after sending a request to the A/C unit. The green LED blinks
three times and stays off during 3 seconds.
In case any of the above errors is detected, the corresponding object will be
sent periodically (with a value of “1”) to the KNX bus. Once the error is over, it
the object will be sent (once) with a value of “0”. The object associated with
each error will be, respectively:
“
[AC] Internal Error: Communication
” (1-Bit).