KLIC-MITT v2
Technical Support:
16
OPERATING TIME
Figure 10.
AC Gateway. Configuration. Operating time.
The operating time of the A/A machine in hours and/or seconds can be known.
The time that A/C unit has been operating, can be known through the 2-Byte object
“[AC] Operating time”
. This object can be read and overwritten during executing time.
The available parameters in ETS are:
Seconds
[
disabled
/enabled
]: enables the 2-Byte object
“[AC] Operating
time (s)”
. This object can be read and overwritten during executing time.
Hours
[
disabled
/enabled
]
:
enables the 4-Byte object
“[AC] Operating time
(h)”
. This object can be read and overwritten during executing time.
Initial Operation Time
:
Keep Current Value
: option enabled by default, which keep the previous
value.
Set New Value
: allows establishing an initial operating time value.
Periodic Sending
[
0
…65535
][
s
][
min
][
h
]: resending period of operating time If
set to 0 the periodic send is disabled.
When operating time object reaches its maximum value, it will be send through KNX
bus (in spite of the fact that the periodical sending has not been configured) and it will
keep this value until the user reset it.