KLIC-DD
Technical Support:
9
Initial configuration:
this functionality allows establishing an initial value for
the A/C unit statuses after installing the system or after recovering from a power
failure. The statuses that may be configured are: ON/OFF, temperature, mode,
fan and swing of the machine.
This initial configuration can be sent both to the KNX bus and to the A/C unit.
Advanced Climate Management:
it allows modifying the setpoint temperature
to be sent to the A/C unit according to the current temperature of the room to
climate (temperature measured by an external sensor, as the touch panel
InZennio Z38i
). The advanced climate management is useful when the
temperature measured by the external sensor is different than the measured
by the A/C unit. The reference for the user is the temperature of the external
sensor and, sometimes, it does not reach the setpoint temperature.
This functionality consists on a periodical analysis of the difference between
the current temperature and the setpoint temperature. If KLIC-DD detects a
more than 1ºC difference between them, it will readjust the setpoint
temperature value adding it the difference with current temperature. KLIC-DD
keeps a memory of these possible deviations, in order to apply them again after
a reset, change of mode, etc.
Logical functions:
KLIC-DD allows enabling and configuring up to 5 different
logical functions. Please read section 3.2.8 for further information.