object “Modified temperature”. The calculation of the new modified temperature
is obtained applying the next formula:
➢
After download or after a user setpoint change (first calculation):
𝑇
𝑚𝑜𝑑.
= 𝑇 + (𝑇 − 𝑇
𝑟𝑜𝑜𝑚
)
➢
Once the first calculation is done, to achieve a more precise adjustment:
𝑇
𝑚𝑜𝑑.
=
𝑇 + 𝑇
𝑚𝑜𝑑. 𝑝𝑟𝑒𝑣𝑖𝑜𝑢𝑠
2
+ (
𝑇 + 𝑇
𝑚𝑜𝑑.𝑝𝑟𝑒𝑣𝑖𝑜𝑢𝑠
2
− 𝑇
𝑟𝑜𝑜𝑚
)
Where
“T
mod.
” is the modified temperature; “T”, user setpoint; “T
room
”, room
temperature sent by an external sensor and
“T
mod previous
”, the previous
modified temperature calculated.
Important:
Since room temperature is used in modified temperature calculation, this
value must be periodically received in order to have an appropriated behaviour of the
advanced climate management.
Examples:
Setpoint upper than room temperature: if the current room temperature stays
constant to 22ºC during the analyze period and setpoint is equal to 25ºC, the
“Modified
Temperature” that will be sent to the A/C machine is:
25 + (25 − 22) = 28
ºC.
If during the next analyze period, the room temperature has not reached user setpoint
yet, and stays constant to 23ºC,
the “Modified Temperature” that will be sent to the A/C
machine is
:
25+28
2
+ (
25+28
2
− 23) = 28,5
ºC
A new modified temperature will be successively calculated until room temperature does
not differ from user setpoint more than 1ºC.
Setpoint lower than room temperature: if the current room temperature stays
constant to 26ºC during the analyze p
eriod and setpoint is equal to 24ºC, the “Modified
Temperature” that will be sent to the A/C machine is:
24 + (24 − 26) = 22
ºC.
Modified temperature will be successively recalculated until room temperature does not
differ from user setpoint more than 1ºC.