ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning
because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data Type (DPT)
Functional Range
Name
Function
0
1 Bit
I
C - - W U
DPT_Switch
0/1
On/Off Sending
Turn ON/OFF the split
1
2 Bytes
I
C - - W U
DPT_Value_Temp
16ºC
–
32ºC
or ac. to param.
Temperature Sending
Value sent to the Split
2
1 Byte
I
C - - W U
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
Mode Sending
0=Aut,1=Ht,3=Cool,9=Fan,14=Dry
3
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
Fan [1byte] Sending
0%Au,1-20%Mi,21-40%Mi/Mid,...
(5 levels)
1 Byte
I
C T - W U
DPT_Scaling
0% - 100%
Fan [1byte] Sending
0%Aut,1-20%Min,21-60%Mid,>60Ma
(3 levels)
4
1 Bit
I
C - - W U
DPT_Switch
0/1
Swing Sending
0=Stop/Step; 1=Swing
5
1 Bit
O
C T R - -
DPT_Switch
0/1
On/Off Reception
Split State (ON/OFF)
6
2 Bytes
O
C T R - -
DPT_Value_Temp
16ºC
–
32ºC
or ac. to param.
Temperature Reception
Value received from the Split
7
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
Mode Reception
Actual Mode:0=Auto,1=Heat...
8
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
Fan Reception
0%Aut,20%Min,60%Mid,100%Max
(3 levels)
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
Fan Reception
0%Aut,20%Mi,40%Mi/Mid,60%Mid..
(5 levels)
9
1 Bit
O
C T R - -
DPT_Switch
0/1
Swing Reception
Swing Status:0=Stopped,1=Swing
10
1 Bit
I
C T - W U
DPT_Switch
0/1
Auto Mode Sending
1=Set Auto Mode;0=Nothing
11
1 Bit
I
C T - W U
DPT_Switch
0/1
Cool Mode Sending
1=Set Cool Mode;0=Nothing
12
1 Bit
I
C T - W U
DPT_Switch
0/1
Heat Mode Sending
1=Set Heat Mode;0=Nothing