KLIC-DD
Technical Support:
17
Mode:
Last, auto, heat, dry, fan, cool or humidify (only for Humidify Dehumidify
models).
Fan:
Last, auto, minimum, medium or maximum.
Swing:
Last, both stopped, normal swing. And the options for Humidify
Dehumidify Indoor Units: Extra swing or both swing.
Moreover, it can be configured the sending of the statuses to the KNX bus and/or to the
A/C split and when they must be carried out:
Send initial configuration to BUS?:
If this sending is enabled ("Yes"), a new
field will appear next: "Delay", where to configure the time, in seconds, KLIC-
DD delays the sending of the statuses to the KNX bus.
Send initial configuration to SPLIT?:
If this sending is enabled ("Yes"), a new
field will appear next:
"Delay"
, where to configure the time, in seconds, KLIC-
DD delays the sending of the statuses to the A/C machine.
Note:
It is highly recommended to establish a delay for the initial configuration sending
to split of at least 1 minute, in order to leave the machine enough time for recovering
itself after a power failure. It is also recommended to establish a higher delay for the
initial configuration sending to the Bus than for the Split. If not, the values could be sent
to the bus twice: the first one, due to the initial statuses sending to the Bus and other due
to a response to the initial configuration to the Split from the split itself.