Characteristic curve
: see section 2.4.1.5.
Start-up type
: see section 2.4.1.4.
ETS PARAMETERISATION
The
“Configuration” screen of each individual heating output contains the following
parameters:
Figure 8.
Heating Control
– Configuration.
Control method
:
[
1 bit
]: the orders to close
(value “0”) and to open (value “1”) the valve must
be received through the one-
bit object “
[HCx] Control Value
– 1 bit
”.
[
1 byte
]:
the orders to close (value “0%”) and to open (value “100%”) the
valve must be received through the one-
byte object “
[HCx] Control Value
– 1 byte
”. This method entails the following parameters as well:
PWM Period
[
5…3600
][
s
] [
1…
15
…1440
][
min
]: sets the PWM cycle time,
i.e., the base time for the PWM modulation.
The device will perform opening and closing orders to the valve
alternatively in order to satisfy the control value.