background image

 

 

 

HeatingBOX

 

http://www.zennio.com

 

               

Technical Support:

 

http://support.zennio.com

 

 

21 

However, if a channel is in state of alarm 1 and alarm 2 is activated, it will be 

ignored and the channel will continue in a state of alarm 1, until the first alarm 

is deactivated when the channel will execute the alarm 2 action. 

ETS PARAMETERISATION 

After enabling “

Alarms

” in the Configuration screen (see section 2.4.1.1), a new tab will 

be incorporated into the tab tree on the left. 

While the parameters of Alarm 1 are displayed by default, parameters of Alarm 2 are 

only shown after thick the corresponding checkbox. 

 

Figure 9. 

Heating Control 

– Alams. 

 

Trigger 

[

0 / 

1

]: sets the value that when received from the KNX bus through 

object “

[HCx] Alarm

” will be interpreted by the actuator as an alarm trigger and 

will therefore initiate the action configured below.  

 

Cyclical Monitoring Period 

[

0…3600

][

s

] [

0

…1440

][

min

] [

0…24

][

h

]: sets every 

how much time, at most, the alarm object should be updated from the bus after 

an  initial  reception  has  already  taken  place.  If  exceeded,  and  for  safety 

reasons, the alarm action will be triggered as well. If this parameter is set to 

zero (default option), the cyclical monitoring function will remain disabled. 

 

Action

: sets the state the output should acquire once a lock order is received. 

The options depend on the control method: 

 

1 bit

: [

No Change 

/ Close Valve / Open Valve

]. 

Summary of Contents for HeatingBOX 24V 4X

Page 1: ...HeatingBOX 24V 230V 4X 8X 4 Output 8 Output 24V 230V Heating Actuator USER MANUAL ZCL4HT24 ZCL8HT24 ZCL 4HT230 ZCL 8HT230 Application programme version 1 2 User manual edition 1 2 _a www zennio com...

Page 2: ...ower Loss 6 2 Configuration 7 2 1 General 7 2 2 Thermostats 9 2 3 Logic Functions 10 2 4 Heating Controls 11 2 4 1 Heating Output n 15 2 4 1 1 Configuration 15 2 4 1 2 Alarms 20 2 4 1 3 Cyclical Monit...

Page 3: ...s in the application programme New module Heartbeat New parameters o Value for open valve o Opening minimum value Output lock due to short circuit overload error Optimisation of thermostat and logic f...

Page 4: ...V or 230V valves depending on the device The most outstanding features are 4 or 8 configurable outputs for controlling electromechanical valves A sole 230 VAC or 24 VAC VDC power input for all outputs...

Page 5: ...ly analogous The main elements of the device are described next Test Prog Pushbutton 5 a short press on this button sets the device into the programming mode making the associated LED 5 light in red N...

Page 6: ...es please refer to the corresponding Datasheet bundled with the original packaging of the device and also available at www zennio com 1 3 START UP AND POWER LOSS During the start up of the device and...

Page 7: ...the General screen it is possible to activate deactivate all the required functionality ETS PARAMETERISATION Figure 2 General screen Heartbeat Periodic Alive Notification disabled enabled 1 incorporat...

Page 8: ...n the left See section 2 2 for details Logic Function disabled enabled enables or disables the Logic Functions tab which contains specific parameters for the case the Logic Functions module is require...

Page 9: ...ermostats depending on the device outputs number which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the HeatingBOX product sectio...

Page 10: ...ion of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after executi...

Page 11: ...ect HeatingBOX 230V reports both errors independently If a short circuit is detected at an output it will be periodically notified through a specific object of that output while overload error is repo...

Page 12: ...k multiple actuators together and to determine the maximum of all of them The optional anti seize protection function which automatically switches the state of those outputs that have been in the same...

Page 13: ...vents have been detected in a period of 3 minutes in any of the channels Three minutes after its activation the value 0 will be sent leaving the locking deactivated Notify When All Valves Are Closed d...

Page 14: ...rmine the above maximum Resending Period 0 30 255 min Note this function ignores those outputs that have not been specifically marked for this purpose see section 2 4 1 Anti Seize Protection disabled...

Page 15: ...ransformed into a PWM signal which is what the actuator actually applies to the output the period of which must be defined by the integrator while under a one bit control such period is assumed to be...

Page 16: ...s on the valve type Valve type Value for Open Valve Control order Output power LED Valve state 1 bit 1 byte Normally closed 1 1 100 Yes Open 0 0 No Closed 0 0 100 Yes Open 1 0 No Closed Normally open...

Page 17: ...orders to close value 0 and to open value 1 the valve must be received through the one bit object HCx Control Value 1 bit 1 byte the orders to close value 0 and to open value 100 the valve must be re...

Page 18: ...s of the valve at the following control orders will be as follows Valve 0 control order 10 Valve 0 Valve 30 control order 10 Valve 20 Valve 0 alarm with action 15 Valve 0 Valve 50 alarm with action 15...

Page 19: ...lue 0 when the output closes and the value 1 when it opens HCx Control Value 1 byte Status only for the one byte control it will send the current control value whenever it changes Note this object cor...

Page 20: ...received at least once before the period expires note this check doesn t take place unless the object has been received at least once In case the object stops being refreshed i e the actuator does not...

Page 21: ...onding checkbox Figure 9 Heating Control Alams Trigger 0 1 sets the value that when received from the KNX bus through object HCx Alarm will be interpreted by the actuator as an alarm trigger and will...

Page 22: ...nd acknowledged if required The options depend on the control method 1 bit No Change Close Valve Open Valve Last Control Value Before the Alarm 1 byte No Change Specific Control Value Last Control Val...

Page 23: ...ion tab section 2 4 1 1 the Cyclical Monitoring tab will be available containing the following parameters Figure 10 Heating Control Cyclical Monitoring Monitoring Interval 1 3600 s 1 30 1440 min 1 24...

Page 24: ...it will recover the last status Custom start up the integrator may select whether the output is required to recover its previous status on the very first start up of the device it will remain closed...

Page 25: ...mpose a delay 0 3600 s 0 1440 min 0 24 h to ensure that this value is sent once the other devices are ready to receive it Note This option is only available if Show Status Object is enabled from Confi...

Page 26: ...curve will be defined as follows see Figure 13 and Figure 14 For control values lower than that of the first point the actual regulation value will be 0 For example in Figure 14 all control values un...

Page 27: ...ion 2 4 1 1 a new tab will be incorporated into the tab tree on the left Figure 15 Heating Control Characteristic Curve Contains the parameters required to define up to three points of the characteris...

Page 28: ...led by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer red and turns yellow From that moment once the button is released the LED...

Page 29: ...ication objects will be ignored Short or long pressing the button will commute the on off state of the output The LED will light in green while the button is being hold The lock and alarm functions as...

Page 30: ...anual Control disabled enabled unless the above parameter has been Disabled the Lock Manual Control parameter provides an optional procedure for locking the manual control in runtime When this checkbo...

Page 31: ...65 95 125 155 185 215 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 Tx Effective Temperature Effective Control Temperature 6 36 66 96 126 156 186 216 1 Byte I C W DPT_HVACMode 1 Comfort 2 Standby 3...

Page 32: ...PT_Heat_Cool 0 1 Tx Mode 0 Cool 1 Heat 22 52 82 112 142 172 202 232 1 Bit O C T R DPT_Heat_Cool 0 1 Tx Mode Status 0 Cool 1 Heat 23 53 83 113 143 173 203 233 1 Bit I C W DPT_Switch 0 1 Tx On Off 0 Off...

Page 33: ...alue_4_Count LF Function x Result 4 bytes Signed 1 Byte O C T R DPT_Scaling 0 100 LF Function x Result 1 byte Percentage 2 Bytes O C T R DPT_Value_2_Count 32768 32767 LF Function x Result 2 bytes Sign...

Page 34: ...enClose 0 1 HCx Control Value 1 bit 0 Open Valve 1 Close Valve 337 349 361 373 385 397 409 421 1 Bit O C T R DPT_Switch 0 1 HCx Control Value 1 bit Status 0 Closed 1 Open 1 Bit O C T R DPT_OpenClose 0...

Page 35: ...00 670760 00 Tx Effective Temperature Effective Control Temperature 6 36 66 96 126 156 186 216 1 Byte I C W DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection Tx Special Mode 1 byte HVAC...

Page 36: ...eat 23 53 83 113 143 173 203 233 1 Bit I C W DPT_Switch 0 1 Tx On Off 0 Off 1 On 24 54 84 114 144 174 204 234 1 Bit O C T R DPT_Switch 0 1 Tx On Off Status 0 Off 1 On 25 55 85 115 145 175 205 235 1 By...

Page 37: ...lue_2_Count 32768 32767 LF Function x Result 2 Byte Signed 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 LF Function x Result 2 Byte Float 325 1 Bit O C T R DPT_Bool 0 1 HC All Valves Are Closed 0 F...

Page 38: ...T R DPT_Switch 0 1 HCx Control Value 1 bit Status 0 Closed 1 Open 1 Bit O C T R DPT_OpenClose 0 1 HCx Control Value 1 bit Status 0 Open 1 Closed 338 350 362 374 386 398 410 422 1 Byte I C W DPT_Scali...

Page 39: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Reviews: