23
The
notification object
will send the
value “1” when the error is detected and the value
“0 once it has been solved, that is, once the external orders are resumed.
Notes
:
Please bear in mind that the monitoring interval must be at least equal or greater
than the PWM control period.
This check doesn’t take place unless the object has been received at least once
.
ETS PARAMETERISATION
After enabling the cyclical
monitoring function from the “Configuration” tab (section
2.4.1.1
), the “Cyclical Monitoring” tab will be available, containing the following
parameters.
Figure 10.
Heating Control
– Cyclical Monitoring.
Monitoring Interval
[
1…3600
][
s
] [
1…
30
…1440
][
min
] [
1…24
][
h
].
Action
: state the output should acquire if the cyclical monitoring is interrupted.
The options depend on the control method:
1 bit
: [
No Change
/ Close Valve / Open Valve
].
1 byte
: [
No Change
/ Specific Control Value
]. When selecting the latter, the
parameter
Control Value
[
0
…100
] shows up to enter the percentage value.
Notify Through Communication Object
[
disabled
/enabled
]: enables the
“
[HCx] Control Value - Error
” binary object, which will send the value “1” in
case the communication has been interrupted
, and the value “0” once the error
is over.