Recommended settings
Ventilation unit
Setting of control unit
Ventilation with heat recovery
Controller,
unless a target value other than 1050 ppm is desired.
Settings
Operation of control unit
Setting of ventilator unit
Sensor
The output signal of the control unit is the
measured value
(whereby 2 V corresponds to 400 ppm and
10 V corresponds to 2000 ppm).
The controller monitors the CO
2
concentrations and increases the ventilation
levels if the setpoint is exceeded.
■
Signal at 0%: 10 V (2000 ppm)
■
Signal at 100%: 2 V (400 ppm)
■
Function of 0-10 V input: control
■
Setpoint:
dependent on the desired CO
2
level.
Example: 4 V (800 ppm).
■
Proportional band: 50% (800 ppm).
■
Integration time: 300 s.
Controller
The output signal of the control unit ensures
the ventilation necessary to achieve
1050 ppm.
The ventilation unit can be controlled via the
0-10 V input.
■
Signal at 0%: 0 V (minimal ventilation)
■
Signal at 100%:
10V (maximum ventilation)
■
Function of 0-10 V input: steer
EN - 11