15 - EN
Additional programme values
Submenu
description
Minimum
Maximum
General
reset
P56
Setting the required air volume in the house.
• nL: ”normal air volume”.
• HL: "high air volume".
nL
HL
HL
Setting the air volume is the starting point for programming the air specifications and set-
ting the fans.
P58
Enter controller priorities.
• 0; The highest air setting is leading INCLUDING the sig-
nals from the analogue inputs
• 1; The highest air setting is leading EXCLUDING the
signals from the analogue inputs
0
1
0
P59
Confirming the presence of an enthalpy exchanger.
• 0; Enthalpy exchanger not fitted
• 1; Enthalpy exchanger with enthalpy sensor.
• 2; Enthalpy exchanger without enthalpy sensor.
0 (= No)
2 (= Yes)
0
Ensure the condensation drain is sealed.
If an enthalpy exchanger without a sensor is selected, then the safety programme will not
be activated and malfunction alerts EA1 & EA2 will never occur.
Menu P5
¨
Setting additional programmes
Additional programme values
Submenu
description
Minimum
Maximum
General
reset
P50
Activation of the open fire programme.
0 (= No)
1 (= Yes)
0
P51
n/a
0 (= No)
1 (= Yes)
0
Leave the value at '0'.
P52
n/a
0
3
2