EN - 14
2.7.4 P menus for the installer
Menus with a dash in 'Minimum' and 'Maximum' value are Reading menus.
Menu P3
¨
Setting ventilation programmes
Ventilation programme values
Submenu
description
Minimum
Maximum
General
reset
P30
Setting the capacity (in %) of the
exhaust fan in absent position.
0% or 15%
97%
nL / HL
15% / 15%
P31
Setting the capacity (in %) of the
exhaust fan in low position.
16%
98%
nL / HL
35% / 40%
P32
Setting the capacity (in %) of the
exhaust fan in medium position.
17%
99%
nL / HL
50% / 70%
P33
Setting the capacity (in %) of the
exhaust fan to high position.
18%
100%
nL / HL
70% / 90%
P34
Setting the capacity (in %) of the
supply fan to absent position.
0% or 15%
97%
nL / HL
15% / 15%
P35
Setting the capacity (in %) of the
supply fan in low position.
16%
98%
nL / HL
35% / 40%
P36
Setting the capacity (in %) of the
supply fan in medium position.
17%
99%
nL / HL
50% / 70%
P37
Setting the capacity (in %) of the
supply fan in high position.
18%
100%
nL / HL
70% / 90%
P38
Current capacity (in %) of the
exhaust fan.
-
-
Current %
P39
Current capacity (in %) of the
supply fan.
-
-
Current %
Menu P4
¨
Reading the temperatures
Temperature values
Submenu
description
Minimum
Maximum
General
reset
P41
Comfort temperature
12
o
C
28
o
C
20
o
C
P45
Current value of T1
(= outside air temperature)
-
-
Current
o
C
P46
Current value of T2
(= supply air temperature)
-
-
Current
o
C
P47
Current value of T3
(= return air temperature)
-
-
Current
o
C
P48
Current value of T4
(= exhaust air temperature)
-
-
Current
o
C