13 - EN
Time delay values
Sub-menu
description
Mini-
mum
Maxi-
mum
General
reset
P26
Note:
Only applies to systems fit-
ted with an rF switch.
Overrun timer for ventilation setting 3 " using
".
• After pressing "
" continuously (> 2 sec.),
the ComfoAir will switch to the high setting
for ‘x’ minutes and then automatically re-
turns to the normal setting.
If any 3-position switch is operated during this
lagging time the ComfoAir will instantly revert
to the ventilation position as set at that time.
1 Min.
120 Min. 30 Min.
P27
Note:
Only applies to systems fit-
ted with a CC Ease panel.
Timer for the Boost setting.
• After pressing “
” continuously (>2 sec.)
on the CC Ease panel, the ComfoAir will
switch to the high setting for 'x' minutes
and then automatically returns to the NOR-
MAL setting
If any 3-position switch is operated during this
lagging time the ComfoAir will instantly revert
to the ventilation position as set at that time.
0 Min.
120 Min. 30 Min.
Menu P9
¨
Status of programmes (from menu P5 and P6 additional programmes)
Status
Sub-menu
description
Activated
P90
Open fire programme active?
Yes (1) / No (0)
P91
Bypass Open?
Yes (1) / No (0)
P94
n/a
Yes (1) / No (0)
P95
Frost protection active?
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)