background image

39

TABLE-2: BOILING TEMPERATURES OF WATER AT CONVERTED PRESSURE

Temperature in Degrees

Inches of Vacuum

Microns

,,

Pounds Per Square Inch

Fahrenheit 

(

°

F)

(Pressure)

212

°

0.00

759,968

14.696

205

°

5.00

535,000

12.279

194

°

9.81

525,526

10.162

176°

16.02

355,092

6.866

158

°

20.80

233,680

4.519

140

0

24.12

149,352

2.888

122

°

26.36

92,456

1.788

104°

27.83

55,118

1.066

86

°

28.75

31,750

.614

80

°

29.00

25,400

.491

76

°

29.10

22,860

.442

72

°

29.20

20,320

.393

69

°

29.30

17,780

.344

64°

29.40

15,240

.295

59

°

29.50

12,700

.246

53

°

29.60

10,160

.196

45

°

29.70

7,620

.147

32

°

29.82

4,572

.088

21

0

29.90

2,540

.049

6

°

29.95

1,270

0245

-9

0

29.97

500

.019685

-24

°

29.99

254

.0049

-35

°

29.995

127

.00245

-60

°

29.999

25.4

.00049

-70

°

29.9995

12.7

.00024

-90

°

29.9999

2.54

.000049

Remaining pressure in system in micron:

1.000 inch = 25,400 microns = 2.540 cm = 25.40 mm .100 inch = 2,540 microns = .254 cm = 2.54 mm 039 inch = 1,000 micron = ,100 cm = 1.00 mm

Summary of Contents for MAC-240

Page 1: ...MOBILE AIR CONDITIONING SYSTEM Model MAC 240 INSTALLATION OPERATION MAINTENANCE MANUAL...

Page 2: ...7 3 3 6 EVAPORATOR FAN 17 3 3 7 HOT GAS BY PASS CONTROL 18 3 3 8 CRANKCASE HEATER 18 3 3 9 REPLACEABLE CORE FILTER DRIER 18 3 3 10 SIGHT GLASS 18 3 3 11 FAN CYCLE HEAD PRESSURE CONTROL 18 3 3 12 CONDE...

Page 3: ...8 2 SERVICE LAMPS 33 8 3 ROTARY BEACON LAMPS 33 9 MAINTENANCE SERVICING 34 9 1 GENERAL MAINTENANCE 34 9 2 INSPECTION PREVENTIVE MAINTENANCE 34 36 9 3 AIR CONDITIONING SYSTEM 37 9 4 MOISTURE IN A REFRI...

Page 4: ...r personal injury and or property damage could happen Please understand and respect those identifications WARNING These units operate on a high voltage with moving parts at high speed which can lead t...

Page 5: ...s as well as trolley s components and accessories The enclosure made of double skin heavy gauge G 90 zinc coated and galvanized steel by the hot dip process of lock forming quality conforming to ASTM...

Page 6: ...the compressor compartment while the system on operation which result safety cutoff to the compressors due to the high pressure in the condenser side refer to the operation part of the manual for mor...

Page 7: ...generator is fully self contained including all controls alarm indications and other operating parameters for the engine and generator The low emission gas generator set is comply ing with internatio...

Page 8: ...SET AUTO MANUAL and START push button The first three push buttons feature LED selected indications Fur ther push buttons provide LCD DISPLAY SCROLL and EVENT LOG VIEW functions Microprocessor control...

Page 9: ...8 D Alarms Shutdowns...

Page 10: ...mps 74 MAX FUSE SIZE CIRCUIT BREAKER Amps 90 UNIT KVA Amps 54 6 CONDENSER COIL Type Inner grooved tubes and enhanced fins Tube Dia Rows Fins per inch 3 8 5 14 Total face area Sq ft 25 EVAPORATOR BLOWE...

Page 11: ...ing Capacity 250 000 BTU hr 115 F ambient temperature Ambient Operating Temperatures 50 F to 125 F Maximum Humidity 100 Airflow 2156 cfm 100 fresh air Static pressure 20 H2 O Altitude To 6561 feet 200...

Page 12: ...s run continu ously in the ambient temperature of 500 C 1220 F at 100 relative humidity environment Auto refrigeration system ensures defrost cycle to prevent the system icing The unit consists of the...

Page 13: ...n as per NEC regulation The engine s control panel has the following monitoring devices a Engine hour meter gauge b Engine oil pressure gauge c Engine temperature gauge d Fuel gauge e Coolant level ga...

Page 14: ...ssor cools it with outdoor air and then causes the refrigerant vapor to condense into a high pressure liquid It may also provide storage for liquid refrigerant in the system Expansion valve The expans...

Page 15: ...14 SCHEMATIC REFRIGERATION DIAGRAM...

Page 16: ...Compressors are conforming to ARI540 STD The compressors are equipped with internal motor protection factory installed crankcase heaters and rubber vibration isolators for quiet and efficient operatio...

Page 17: ...s Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral A refrigerant enters the outer openings as one of the spirals orbits The open passages are seale...

Page 18: ...are statically and dynamically balanced to operate at minimum noise and vibration Fan blades are designed with appropriate pitch angle which result in maximum airflow through the condenser coil 3 3 4...

Page 19: ...and provides a mean for checking the system refrigerant 3 3 11 Fan Cycle Head Pressure Control The capacity of air cooled condensers varies with the difference between condensing temperature and cond...

Page 20: ...8 15 06 05 02 EVAPORATOR COIL 03 CONDENSER COIL 04 EXPANSION VALVE 05 VIBRATION ELIMINATOR 06 HGBP LINE 07 VIBRATION ELIMINATOR 08 MUFFLER 09 BALL VALVE 01 COMPRESSOR 04 07 08 09 3 4 REFRIGERATION SYS...

Page 21: ...plied air The signals are transmitted to the microprocessor board which will then manage the operation of the compressors in the unit Cooling or compressor operation can only be able to start if the f...

Page 22: ...ing of 3 minutes Both compressors will operate at the same time in the first 2 minutes and the last 5 minutes in each 13 minutes interval There will then be 2 compressors running for a total of 7 minu...

Page 23: ...the device is set to show the motor speed in RPM and the drive s output in AMPS The on off command is set to be controlled through switching contacts in the main control panel of the ACU However the...

Page 24: ...ton Used to decrease the parameter values or go back to the previous information displayed on the LCD window 2 6 ON OFF Button Used to shut off or start the system s control 7 Menu Button Used to acce...

Page 25: ...give power to the lamps 25 Beacon Lamp Switch This switch will turn ON OFF the beacon lamp on top of the unit provided that the fuel level is more than 30 If fuel level is less than 30 then the beaco...

Page 26: ...r details please see the more description of test operation in the generator set manual 5 Start Button This button is only active in manual or test mode Pressing this button in manual or test mode wil...

Page 27: ...oints to ensure safe and reliable operation a Check generator engine oil level Remove engine oil dipstick and check oil level mark on it Add oil to bring it to full level mark CAUTION NEVER OPERATE TH...

Page 28: ...The fuel tank has drains in the side of the tank Drain water and foreign material at least weekly k Remove the air conditioning duct from storage box located below the trailer and near to supply blow...

Page 29: ...rator section and ACU circuit breaker inside the main control panel At this point the LCD display of the user interface board in the main control panel will be illuminated and the power button will be...

Page 30: ...ll the compressors will stop and the supply fan shuts off after a pre set timing of 30 seconds b To bring the generator to stop turn the Start Control Switch in OFF position The generator engine will...

Page 31: ...ondition is corrected g SP TR OUT OF RANGE This fault is caused by an open or shorted suction pressure transducer Compressors are stopped or will not be able to operate Number shown with the fault cor...

Page 32: ...nal Overload Relay Contact of compressor opened c Cond Fan motor thermal contact is open CORRECTIVE MEASURE Check and Re tighten wiring connec tion Remove the clog or straighten the hose Replace Relay...

Page 33: ...upply in the control circuit thereby cutting OFF power to the motors The voltage monitor relay will re set automatically when power is brought back to normal conditions The trip settings and other det...

Page 34: ...or engine is not running or in stand by mode If in case the generator engine is running and the operator decides to check the fuel level the generator controls may stop the engine if the push to check...

Page 35: ...checking C Engine oil specifications Refer to the Genset Manual for engine lubrication specifications and requirements D Fuel Refer to the Genset Manual for engine fuel specifications and requirement...

Page 36: ...18 Inspect system for restrictions X 19 Inspect clamps for tightness X 20 Inspect for corrosion X 21 Inspect muffler for security X X X X 22 Inspect that battery electrolyte level covers plates X 23...

Page 37: ...contact cleaner as required X 51 Check all pressures temperatures as applicable and satisfy the operation performance X 52 Ensure that the towing bar is in the vertical position and locked X 53 Ensur...

Page 38: ...e with the Montreal Protocol venting refrigerant to the atmosphere is not permitted Never vent refriger ant from the system or Freon cylinders to atmosphere Always use a refrigerant recovery and recyc...

Page 39: ...n the form of sludge can plug fine strainers expansion valves and capillary tubes Because it usually contains acids sludge corrodes whatever it clings to accelerating system damage Only use fresh oil...

Page 40: ...55 118 1 066 86 28 75 31 750 614 80 29 00 25 400 491 76 29 10 22 860 442 72 29 20 20 320 393 69 29 30 17 780 344 64 29 40 15 240 295 59 29 50 12 700 246 53 29 60 10 160 196 45 29 70 7 620 147 32 29 8...

Page 41: ...Continue evacuation until obtaining the desired vacuum reading on both gauges 6 When evacuation is complete close the valves on the manifold gauges tightly remove the line from the vacuum pump and con...

Page 42: ...ing a refrigeration recovery system compatible with R22 pump refrigerant from the system and dispose 3 Replace drier if necessary see sight glass for moisture indication 4 Correct leak as described be...

Page 43: ...on cylinder 5 Purge the charging line and tighten the connection 6 Check the tubing connections between the R 22 Freon cylinder and the charging valve for leaks 7 Open the valve on the Freon cylinder...

Page 44: ...43 10 EQUIPMENT DIMENSIONAL DETAILS Model No MAC240FZ600...

Page 45: ...44 11 MAIN CONTROL PANEL COMPONENT LAYOUT...

Page 46: ...45 12 MAIN CONTROL PANEL COMPONENT PARTS LIST...

Page 47: ...TAINLESS STL 3 8 DIA S S EA 8 80002994 DOOR STOP WITH PANEL MOUNTING DEVICE EA 6 80003215 SCREW 3 8 8 32TPI EA 40 80003280 SCREW 5 16 DIA 7 8 LG HEX HD 18TPI TAPTITE EA 53 80003404 SCREW 400 8 PHL TRU...

Page 48: ...NOM EA 4 80014711 NON METALLIC LIQ TIGHT CONDUT FITTINGS NMLT 3 8 EA 4 80014713 NON METALLIC LIQ TIGHT CONDUT FITTINGS NMLT 3 4 EA 4 80014714 NON METALLIC LIQ TIGHT CONDUT FITTINGS NMLT 1 EA 4 8001710...

Page 49: ...C EA 1 80035390 N O CONTACT BLOCK HARMONY STYLE 4 3A 240V EA 3 80035391 N C CONTACT BLOCK HARMONY STYLE 4 3A 240V EA 1 80035654 RELAY DPDT 2 FORM C 24V 50 60HZ EA 6 80035656 RELAY DPDT 2 FORM C 240V 5...

Page 50: ...X 13 16 AR4 EA 1 80045371 LABADH ADHESIVE 7 16 X 13 16 AR5 EA 1 80045372 LABADH ADHESIVE 7 16 X 13 16 AR6 EA 1 80045373 LABADH ADHESIVE 7 16 X 13 16 AR7 EA 1 80045374 LABADH ADHESIVE 7 16 X 13 16 AR8...

Page 51: ...SECTION EA 1 80104513 LBL FILTER SECTION EA 1 80104640 HEXAGON NUT M6 x 5mm S S DIN 934 EA 20 80104653 WASHER M6 x 6 4mm S S DIN 125 EA 20 80106000 BLOWER MOTOR 13KW 460 3 60hz TEFC ptc 3600RPM EA 1 8...

Page 52: ...159 80107949 SPRING WASHER B 8 VZ GAL EA 19 80107950 SPRING WASHER B 10 VZ EA 8 80107951 SPRING WASHER VZ DIN 127 B 12 EA 8 80108510 HANDLE 117 GN 528 BLACK EA 1 80108521 3D HINGE RIGHT 217 9405 EA 4...

Page 53: ...T AR9 57 AR10 24V ac TO MB CR1 1A VENT COOL 9 43 SW2 72 42 ATB 1 GEN SET START GEN RUN FAN OFF 41 40 SW1 1A 1B 460V 3 230V 5 500VA A13 TO MB A14 CR1 GEN SET CONTROL PANEL gen set 84 85 ES ES 1A ATB 1B...

Page 54: ...0NO 18B 13NO BMR1 FMC2 18A 9NO 8NO 8NC AR3 48 FMC1 5C 4C 6C 1C 3C 2C 3B 5O 4O 4B 6O HGS2 CC2 3A 4A HGS1 2O 3O 1O CC1 BMCA 1A AR5 3B AR2 2A AR8 2A CB2A 1 HPS2 P HPS1 CB1A 1 P A12 S FAN ENABLE 71 A17 VF...

Page 55: ...ND CONNECTION CONNECTED EARTHING ATB LVTB AUXILIARYTERMINAL BLOCK CONTROL WIRING CONTROL WIRING TERMINAL BLOCK HVTB L2 L3 L1 S1 MAIN POWER CONNECTION TERMINAL BLOCK TOGGLE SWITCH SW SELECTOR SWITCH NO...

Page 56: ...55 16 UNIT OVERALL VIEW...

Page 57: ...56 UNIT REAR SIDE GENERATOR SECTION...

Page 58: ...57 OPTIONAL DOWN DISCHARGE PLENUM EXTENSION FLEXIBLE DUCT STORAGE BOX...

Page 59: ...58 DIESEL FILLING POINT FUEL GAUGE...

Page 60: ...59 COIL SECTION...

Page 61: ...60 FAN MOTOR ASSEMBLY...

Page 62: ...61 CONDENSER SECTION...

Page 63: ...62 OPERATIONAL PANEL...

Page 64: ...63 MAIN CONTROL BOX...

Page 65: ...64 VFD GENERATOR...

Page 66: ...65 GENERATOR DISPLAY PANEL...

Page 67: ...66 GENERATOR SECTION...

Reviews: