28
5.2 STARTING THE GENERATOR ENGINE
a) Switch “ON” the isolating switch of the DC battery in the generator set section. The “lever” should be
pointing towards the operator to be in “ON” position.
b) Turn the key provided in the generator module to switch “ON” power to the module. The module’s LCD display will be
illuminated and information appearing on it.
c) Set the module in “auto” mode by pressing first the “Stop/Reset” button then followed by the “Auto Mode”
button .
d) In the main control panel, set the “Start Control Switch” to “GEN ON” position. The generator engine
should then start at this point.
5.3 STARTING THE ACU (AIR CONDITIONING UNIT)
a) Switch “ON” the mains circuit breaker (in the generator section) and ACU circuit breaker (inside the main control
panel). At this point, the LCD display of the user interface board in the main control panel will be illuminated and the
power button will be lighted up.
b) Turn the “Start Control Button” to “FAN” position to bring the ACU system in standby mode.
c) Push the “ON/OFF” button on the user interface board to bring the system’s control in the operation mode.
The “ON” LED positioned above right of the button will light up and the LCD display will show “STARTING”. After a
minimum time of 1 minute, the supply fan motor will start.
d) Turn the “Mode Control Switch” to "COOL" position to operate the compressors (cooling mode). The
cooling system will be allowed to start if the conditions described under 4.2.1 “Cooling Control” in this manual are
satisfied.
e) Select the desired cooling level (Low, Medium or High) through the “Cooling Level Switch”.
Summary of Contents for MAC-240
Page 1: ...MOBILE AIR CONDITIONING SYSTEM Model MAC 240 INSTALLATION OPERATION MAINTENANCE MANUAL...
Page 9: ...8 D Alarms Shutdowns...
Page 15: ...14 SCHEMATIC REFRIGERATION DIAGRAM...
Page 44: ...43 10 EQUIPMENT DIMENSIONAL DETAILS Model No MAC240FZ600...
Page 45: ...44 11 MAIN CONTROL PANEL COMPONENT LAYOUT...
Page 46: ...45 12 MAIN CONTROL PANEL COMPONENT PARTS LIST...
Page 56: ...55 16 UNIT OVERALL VIEW...
Page 57: ...56 UNIT REAR SIDE GENERATOR SECTION...
Page 58: ...57 OPTIONAL DOWN DISCHARGE PLENUM EXTENSION FLEXIBLE DUCT STORAGE BOX...
Page 59: ...58 DIESEL FILLING POINT FUEL GAUGE...
Page 60: ...59 COIL SECTION...
Page 61: ...60 FAN MOTOR ASSEMBLY...
Page 62: ...61 CONDENSER SECTION...
Page 63: ...62 OPERATIONAL PANEL...
Page 64: ...63 MAIN CONTROL BOX...
Page 65: ...64 VFD GENERATOR...
Page 66: ...65 GENERATOR DISPLAY PANEL...
Page 67: ...66 GENERATOR SECTION...