2.3.1 UNIT SPECIFICATION SUMMARY
1. GENERAL
•
Length (overall): 141.7 inches (3600mm)
•
Width (overall): 86.9 inches (2210 mm)
•
Height (overall): 104.5 inches (2654mm)
•
Weight (approximate): 8800 lbs (4000 kg)
•
Storage Temperature: 40
°
F to 120
°
F(clean and dry place)
•
Fuel Tank Capacity(approximate): 104 gallons (396 I)
2. POWER GENERATING SYSTEM
•
Make: WESTAC (DEUTZ) Air cooled diesel engine generator.
•
Model: WPDZ72 (WP07-A76217) / F6L914
•
Rating: (85KVA/ 68KW @ NTP)
•
Voltage: 460 Volts/ 3 Phase / 60HZ
3. AIR CONDITIONING SYSTEM
•
Cooling Capacity: 280,000 BTU/hr. @ 95°F ambient temperature
•
Cooling Capacity: 250,000 BTU/hr. @ 115°F ambient temperature
•
Ambient Operating Temperatures 50°F to 125
°
F
•
Maximum Humidity: 100%
•
Airflow=2156 cfm -100% fresh air
•
Static pressure= 20" H
2
O
•
Altitude: To 6561 feet (2000m)
•
Refrigerant: R22
4. VEHICLE/ UNIT ENCLOSURE
•
Completely self contained enclosure, constructed of base rail, post and double skin aluminum and steel panels. The
whole unit is mounted on heavy duty trolley. All the service doors are hinge mounted with air tight turn buckle lock.
These light weight aluminum construction doors are ready to access component for service and inspection.
•
Parking drum brakes in trunnion axle wheel is activated by raising the towing bar and deactivated by lowering the
towing bar.
•
Maximum operating trolley speed 15km/ hr
Summary of Contents for MAC-240
Page 1: ...MOBILE AIR CONDITIONING SYSTEM Model MAC 240 INSTALLATION OPERATION MAINTENANCE MANUAL...
Page 9: ...8 D Alarms Shutdowns...
Page 15: ...14 SCHEMATIC REFRIGERATION DIAGRAM...
Page 44: ...43 10 EQUIPMENT DIMENSIONAL DETAILS Model No MAC240FZ600...
Page 45: ...44 11 MAIN CONTROL PANEL COMPONENT LAYOUT...
Page 46: ...45 12 MAIN CONTROL PANEL COMPONENT PARTS LIST...
Page 56: ...55 16 UNIT OVERALL VIEW...
Page 57: ...56 UNIT REAR SIDE GENERATOR SECTION...
Page 58: ...57 OPTIONAL DOWN DISCHARGE PLENUM EXTENSION FLEXIBLE DUCT STORAGE BOX...
Page 59: ...58 DIESEL FILLING POINT FUEL GAUGE...
Page 60: ...59 COIL SECTION...
Page 61: ...60 FAN MOTOR ASSEMBLY...
Page 62: ...61 CONDENSER SECTION...
Page 63: ...62 OPERATIONAL PANEL...
Page 64: ...63 MAIN CONTROL BOX...
Page 65: ...64 VFD GENERATOR...
Page 66: ...65 GENERATOR DISPLAY PANEL...
Page 67: ...66 GENERATOR SECTION...