High temperature detection max. value, unit is , when either temperature sensor
is higher than this value, the device will turn off the relay and send NOTIFICATION
CC.
0, disable this function
20-60, the high temperature value
℃
6.Advance Config Parameters
Parameter Size
Description
Default
Value
0x02(2)
1
16
Over current detection max. value, unit is A. When detected current is over this
value, the device will turn off the relay and send NOTIFICATION CC.
0, disable over current detection
5-16, over current detection max. value
0x03(03)
1
1
Vibration level
triggered by pressing buttons
0, disable vibration and buzzer
1, Low Level
2, High Level
and buzzer level
0x04(4)
1
1
Whether to recover to settings before power failure or power reset
0, use default settings
1, recover to settings before power failure or power reset
1
Lifeline
AGI_LIFE_LINE
(
0x0001
)
0
Lifeline
GroupID
NAME
Profile
Max nodes
description
Parent
Menu
Monitor Set
Other Set
Other Set
EndPoint02
0x14(20)
1
When to report voltage change absolute threshold, unit is 1 V
0, disable to report
1~10, report when absolute threshold is 1~10
2
0x15(21)
4
Time interval value for periodic active report of Meter
60-2678400 (31 days), unit is S
600
(10mins)
0x12(18)
1
5
0x13(19)
1
When to report current change absolute threshold, unit is 0.1A
0, disable to report
1~10, report when absolute threshold is 1~10
10
0x17(23)
1
This parameter defines which sensor temperature will be displayed on Home page.
0x00: indoor air temperature
0x01: external temperature (floor temperature)
0
0x16(22)
1
The OLED display brightness when operate the device.
0, low level
1, mid level
2, high level
1
Other Set
Other Set
None
None
None
None
When to report power change absolute threshold, unit is W
0, disable to report
1~100, report when absolute threshold is 1~100
0x11(17)
1
300
(5mins)
Time interval value for periodic report of temperature, humidity, unit is S
0, disable to report
30~28800, report when time interval value is 30~28800
None
Note: the EndPoint01 has equivalent effect of root function.
2
Heat Set
5
AGI_CONTROL_KEY01
(0x2001)
Transfer Command Class THERMOSTAT_SETPOINT_SET
THERMOSTAT_MODE_SET
to control other temperature control devices when operation
changes
EndPoint01:
1
Lifeline
AGI_LIFE_LINE
(
0x0001
)
0
Lifeline
GroupID
NAME
Profile
Max nodes
description
1
Lifeline
5
AGI_LIFE_LINE
(
0x0001
)
1.Send Command Class
DEVICE_RESET_LOCALLY_NOTIFICATION to associated
devices of this group when factory reset the device.
2.Send Command Class THERMOSTAT_SETPOINT_REPORT,
THERMOSTAT_MODE_REPORT,
THERMOSTAT_OPERATING_STATE_REPORT to associated
devices of this group When operation mode and temperature
change.
3.Send Command Class NOTIFICATION_REPORT to
associated devices of this group when over current, over heat
detected
4.Send Command Class METER_REPORT to associated
devices of this group to report metering parameters.
Root device
Group ID
NAME
Max nodes
description
Profile
0x10(16)
1
2
When to report temperature relative change threshold value actively, unit is 0.1
℃
0, disable to report
2-10, report when the threshold value is 2-10
None
0x0E(14)
1
2
Set the mode after the drying mode ends
0x00 = OFF
0x01 = Manual mode (comfort mode)
0x02 = Auto mode (energy save mode)
0x03 = Away mode
Dry Mode
Schedule
0x0D(13)
1
30
Set how long the dry
ing
mode lasts
5~100, unit is minute
Dry Mode
Schedule
0x0A(10)
1
1
Temperature control reference selection
1, room sensor
2, floor sensor
3, room+floor sensor
0x0B(11)
1
0
ROOM SENSOR temperature compensation setting
-10~10, unit is 0.5
℃
0x0C(12)
1
0
FLOOR SENSOR temperature compensation setting
-10~10, unit is 0.5
℃
Other Set
Other Set
Other Set
0x09(9)
1
1
Select floor temperature sensor type
1, NTC/10K B(25/50
℃)
=
3950
2, NTC/15K B(25/50
℃
)=3950
3, NTC/50K B(25/50
℃
)=3950
4, NTC/100K B(25/50
℃
)=3950
Other Set
5.Association
YES
YES
YES
YES
COMMAND_CLASS_SUPERVISION
COMMAND_CLASS_SENSOR_MULTILEVEL
COMMAND_CLASS_ASSOCIATION
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION
COMMAND_CLASS_ASSOCIATION_GRP_INFO
V1
V5
V2
V3
V1
0x08(8)
1
0
Auto mode (Energy save mode) temperature schedule
0, use schedule set by user
1, use Energy_Save_Heating temperature set by THERMOSTAT_SETPOINT_SET
None
0x07(7)
1
5
Temperature control hysteresis value setting, setting range 0.5
℃
-
2
℃
5-20, unit is 0.1
℃
0x06(6)
1
45
Monitor Set
Monitor Set