7. MONITOR SET

The function of monitor set is real time monitor of over current, over heat and freezing, on Home interface, short 
press          MONITOR SET to enter into monitor set interface as follows: 

For configuration method and modification, please refer to Automatic Mode 
(Energy Save Mode) Schedule:

6.Dry Mode Schedule

For example, in order to quickly dry the water in the bathroom, the device can be set to quickly heat in a short 
time to dry the floor. Enter the configuration interface as follows:
          
Duration: set how long the dry mode lasts
After Mode: set the mode after the drying mode ends
Remain: shows the remaining time of the drying mode

D means date, M means month, Y means year (2019-2099).
Start and end mean away time.
To enter into the setting interface and setting method, please refer to the 1.4 
Auto Mode (Energy Save Mode) Schedule.

F

On Auto Day Schedule interface, short press button 

     

  to select the time or 

temperature that you would like to modify, then short press move up and move 
down buttons  

       

   to modify value, then short press button 

    

to save 

and quit, short pressing button  

    

 only quits without saving.

F

5.Away Mode Schedule

User can set time to leave home and time to go home according to the requirements of themselves, and set how 
the device will control the temperature during this period.
1.If away mode has already been activated, the end time for away mode is valid, the device will execute Away 
Mode Temperature Schedule before the end time.
2.If away mode has already been activated, the values of end time for away mode are set as 0, the device will 
always execute current set temperature with no time limitation. The device will consider the mode as anti-
freeze mode, the recommended temperature setting is 4-10

℃.

For each schedule, the latter time should be later than the former time, otherwise saving will fail with the error 
remind “Time setting error!!!”. The default time schedules are as follows:
Monday ~ Friday
7:30,24

  ~ 12:00,20

  

18:00,16

 ~  22:30,18

  

Saturday

~

Sunday

7:30,24

  ~  12:00,20

  

18:00,18

 ~  22:30,18

Schedule setting method 2: 

on Home Interface, meanwhile the device is under Auto Mode 

    

 

 

, short press 

button 

     

  to enter into Auto Mode Schedule weekly setting interface quickly:

On Auto Mode Schedule weekly setting interface, use buttons   

    

and 

   

  to enter into schedule setting of a 

certain week as follows:

Hysterersis

To prevent the undulation of sensor temperature when the sensor temperature is approaching the set

 

temperature, which will cause that the controller may keep switching on/off the relay. Here hysterersis enables 
the controller to control the relay only when the sensor temperature is a little bit lower than the set temperature, 
this value can be set. This hysterersis only valid when the control type is single sensor, please refer to the part 
Control Type.

For instance, when hysterersis is set as 0.5 degree, then only when current sensor temperature is 0.5 degree 
lower than the set temperature, will the controller heat, if the sensor temperature >= set temperature, the 
controller will not heat.

 

(0.5°C by default)

RoomTemp Alarm 

If room temperature is over the set value, the relay will be forced to off by the device, and over heat alarm will be 
reported to the associated devices, meanwhile the buzzer or vibrator will beep 3 times every 10 seconds. The 
over heat alarm function can be disabled, which can be set directly through the device. Or can be configured 
through Advance Config parameter 6 by setting the value as 0 to disable the function, please refer to the part 
“Advance Config”.
Over heat alarm interface is as follow:

(

by default)

45°C 

Note: to cancel over current alarm or over heat alarm, just press and hold 
button  

     

 for over 3 seconds or reset power of the device. After cancel 

manually, the relay will show heating forbidden icon 

     

  within 120 

seconds, but other operations are allowed.

Max Current

If current is over the set value, the relay will be forced to off by the device, and the state will be reported to the 
gateway. The over current alarm function can be disabled, which can be set directly through the device. Or can 
be configured through Advance Config parameter 2 by setting the value as 0 to disable the function, please 
refer to the part “Advance Config”. 

 (16A by default)

Short press button

      

to select the item would like to modify, then short press 

move up and move down buttons                to modify value of selected item, then 
short press button

  

   to save and quit, short pressing button  

    

only quits 

without saving.

F

Window Open Detect

Once the device is powered on and stable, referring to the room temperature sensor, if the temperature 
decreases to the threshold of this setting, the window open mark will be enabled, the relay will be forced to turn 
off to save energy, then the icon        will appear.

After window open mark is enabled, if the temperature increases to the threshold of this setting in 3 minutes, 
the window open mark will be disabled.

Once the window open mark is enabled, it will be disabled after 10 minutes, and the working mode will change 
to         (OFF mode).

 The threshold value of this parameter can also be configured through Advance Config parameter [26]. 0 means 
this function is disabled.
Note: this function will work better when the device is installed beside the window or door.

 (disabled by default)

Summary of Contents for SR-ZV9092A

Page 1: ...50 3950 default 2 NTC 15K B 25 50 3950 3 NTC 50K B 25 50 3950 4 NTC 100K B 25 50 3950 Control type means which temperature sensor the device refers to when it adjust temperature Room sensor adjust tem...

Page 2: ...he device is under idle status Manual Comfort Mode the device will control the heating system according to current set temperature The temperature can be set by move up and move down button on the Hom...

Page 3: ...ersis enables the controller to control the relay only when the sensor temperature is a little bit lower than the set temperature this value can be set This hysterersis only valid when the control typ...

Page 4: ...de After scanning to add the device reset power of the device or waiting for a while the device will be added to the gateway automatically Please find the QR code on the casing of the device Removing...

Page 5: ...TAT_HEATING Always On Slave AOS Yes 2 Technical Specifications SENSOR MULTILEVEL Type support Air temperature Scale Celsius Z Wave Technical Specifications 1 Supported Notification Repoert and Sensor...

Page 6: ...Set 5 AGI_CONTROL_KEY01 0x2001 Transfer Command Class THERMOSTAT_SETPOINT_SET THERMOSTAT_MODE_SET to control other temperature control devices when operation changes EndPoint01 1 Lifeline AGI_LIFE_LI...

Page 7: ...be away from sunlight and sources of direct heat We recommend installing the device approximately 1 5 meters above the floor Troubleshooting 1 External floor sensor temperature tolerance is too big Po...

Reviews: