Status Functions
The status functions available via Modbus are listed below. The registers are accessed using
Modbus function 1.
Address
Access
Descriptions
01001
Read Only
System Started (1); Stopped (0)
01002
Read Only
Verometer Filling (1); Not Filling (0)
01003
Read Only
Proportional to Flow Mode (1); Proportional to Time Mode (0)
01004
Read Only
Flow Signal Type - Pulse (1), Analog (0)
01005
Read Only
Pulse Mode: PPM (1); PPS (0)
01006
Read Only
Load Cycle Active (1) / Not Active (0) -- Liquid system only
01007
Read Only
No-Flow Standby Active (1); Operating Normally (0)
01008
Read Only
Remote inhibit active (1); inactive (0)
01009
Read Only
Low flow shutoff active (1); inactive (0)
01010
Read Only
Flow no signal active (1); inactive (0)
01011
Read Only
Power Up (1) / No Power Up (0) since last coil read
01012
Read Only
Parameter Change (1) / No Parameter Change (0) since last coil read
01013
Read Only
New HOU/LOU Data Available (1) / not available (0) since last coil
read
01014
Read Only
Metric Units (1); English Units (0)
01015
Read Only
Memory Module Present (1); Not Present (0)
01016
Read Only
Resume Operation on Power-Loss Enabled (1); Disabled (0)
01017
Read Only
Low injection rate alarm enabled (1); disabled (0)
01018
Read Only
High injection rate alarm enabled (1); disabled (0)
01019
Read Only
Bulk Tank Low Alarm Enabled (1) / Disabled (0)
01020
Read Only
Bulk Tank High Alarm Enabled (1) / Disabled (0)
01021
Read Only
Low inlet pressure alarm enabled (1); disabled (0)
01022
Read Only
High inlet pressure alarm enabled (1); disabled (0)
01023
Read Only
Signal Alarms Enabled (1) / Disabled (0)
01024
Read Only
Verometer Alarms Enabled (1) / Disabled (0)
01025
Read Only
Pump Alarms Enabled (1) / Disabled (0)
01026
Read Only
Controller Alarms Enabled (1) / Disabled (0)
01027
Read Only
Odorant Output Enabled (1); Disabled (0)
01028
Read Only
Redundancy Enabled (1); Default (NBS Output) (0)
01029
Read Only
NJEX Backup System Output Active (1); Inactive (0) -- always reads
'0' if redundancy is enabled
01030
Read Only
Primary System (1); Backup System (0) -- always reads '0' if
redundancy is disabled
01031
Read Only
Redundancy Status Odorizing (1); Standby (0) -- always reads '0' if
redundancy is disabled