EM-0146-8
- -
18
2.7.5 Sensor terminals
Table 2.7f Pressure Sensor/Thermistor Terminals
Type Symbol
Name
Function/Use
1
Pressure Sensor Power
Supply
Supplies DC 4.9 to 5.2 V power to the pressure sensor.
2
Pressure Sensor Input
Receives the output voltage of the pressure sensor.
(0.5 to 4.5 V = 0 to 35 MPa)
3
Pressure Sensor
Common
Common terminal for the pressure sensor.
4
Pressure Sensor Shield
Wiring for a measure against radiated noise.
5
Thermistor Input - 1
6
Thermistor Input - 2
Receives the output voltage of the sensor for monitoring the
motor’s internal temperature.
Analog I/O
Te
rminal
7 Reserved
2.7.6 Main circuit terminals
Table 2.7g Main Circuit Terminals
Type Symbol
Name
Function/Use
R/L1
S/L2
T/L3
AC Power Input
Connects to a commercial power supply
- AMSE-4**-**-* : 3-phase AC 380 to 480 V
- AMSE-**-**-* : 3-phase AC 200 to 220 V / 50Hz
: 3-phase AC 200 to 240 V / 60Hz
U
V
W
Motor Output
Connects to the motor.
Note) Match the U, V, and W phases for cable connection.
N/-
Not connected
Connection is not required.
P1
Not connected
Short-circuited to P/+. Do not remove the short bar.
P/+
Regenerative Resistor
Connection
PR
Regenerative Resistor
Connection
Connects to the attached regenerative resistor.
* The wiring method (series or parallel) varies depending
on the models.
High V
olt
age
Powe
r Ca
ble
Ground
Be sure to connect the ground wire.
2.7.7 Control power terminals
The main circuit terminals R/L1 and S/L2 are internally connected with R1/L11 and S1/L21 (control
power terminals in the lower low). By default, the lower terminal block is connected with the upper
terminal block (control power terminals) via short bars; the control power is turned on at the same
time as the main circuit power is turned on. To keep the control power active at the time of error
detection, remove both short bars (shown below) and provide the control power separately.
(1) Remove the lid.
(2) Remove the screws.
(3) Remove the short bars.