background image

035-20401-001 Rev. A (0904)

Unitary Products Group

9

LED DIAGNOSTIC INDICATORS

The control includes two LED’s that display various types of diagnostic
information. LED1 is red and LED2 is green. The location of the LED’s
is shown in Figures 11 & 14. These LED’s are used to display opera-
tional mode, status, and fault information.

OPERATIONAL MODE DETECTION

The control can be used in a variety of applications including heat
pumps and air conditioners with modulating compressors. The control
uses various inputs to determine the proper mode of operation. 

It looks for the presence of a reversing valve connected to the RV and
RVG terminals to determine if it should operate as a heat pump or an air
conditioner. If the reversing valve is not connected, the control will not
operate in the heat pump mode. The control senses the reversing valve
loads and determines the operational mode each time power to the
control is cycled.

The control also senses the connections that are made to the M, M1,
and M2 terminals and determines the correct operational mode for the
control. This is done each time power to the control is cycled. There-
fore, it is important for this 2-stage system that no loads be attached to
the M1 terminal of the control. Incorrect system behavior could result.

IMPORTANT: Do not connect any loads to the M1 terminal of the
control. Incorrect system behavior could result.

OPERATIONAL MODE DISPLAY

The control will display its active operational mode using the onboard
LED’s when the TEST pins are connected while no thermostat signals
are energized. See Table 2. The control will display the operational
mode as long as the TEST pins are shorted and no thermostat signals
are energized. When the TEST pin short is removed, the control will
return to normal LED displays. The X/L output will be energized (with
the number of flashes corresponding to the active defrost curve) while
the operational mode is displayed. For example, if defrost curve 2 is
active, the X/L output will be energized with two flashes while the oper-
ational mode is being displayed on the LED’s.

If the control displays an operational mode other than LED2 (Green)
ON and LED1 (Red) 3 flash indicating a heat pump with a scroll 2-stage
compressor, an error condition exists. Check all wiring of the reversing
valve (RV and RVG terminals) and compressor outputs (M, M1, and M2
terminals). Cycle 24 VAC power to the control and check the opera-
tional mode again.

STATUS MODE DISPLAY

The control also provides status codes using the LED’s. Status codes
indicate the state of operation of the unit but do not represent a fault.
Table 3 describes the LED displays during status codes. Status codes
will not be displayed when a fault code is present.

During the following conditions, the control will not energize the X/L out-
put.

FAULT CODE DISPLAY

X/L Output

The X/L terminal of the heat pump control is typically connected to the
X/L input of the room thermostat. The thermostat uses this signal to
notify the homeowner of a problem with the heat pump using an LED or
LCD display. When the control energizes the X/L terminal, the thermo-
stat displays the flash code so the homeowner can see it.

The heat pump control informs the homeowner of the type of condition
that is present using flash codes. Table 4 shows the condition catego-
ries and the corresponding X/L flash codes.

The control will continue to energize the X/L output for fault codes hav-
ing an X/L code of 4 flashes even after the thermostat calls are
removed. The control does this to notify the installer or homeowner that
a significant problem with the wiring or system configuration is present
and needs to be corrected.

The control will continue to energize the X/L output until the condition
that caused the fault condition no longer exists.

LED Display

The control will display any fault code that is currently active using the
LED’s. The control will display the fault code, pause two seconds, and
display the fault again. The control will continue the fault code display
until the condition that caused the fault code no longer exists. If multiple
fault codes are present at the same time, the control will display only
the most recent fault. The other active errors may be accessed from
memory using the LAST ERROR pushbutton.

Operational Fault Codes

Table 5 shows the operational faults that the control can detect. The
control displays this type of error by flashing LED1 (Red) only. LED1
(Green) is not energized. These faults typically occur when the heat
pump has been operating and a problem occurs.

TABLE 2: 

Operational Mode Display

Operational Mode

LED1
(Red)

LED2

(Green)

Heat Pump

ON

Air Conditioner

OFF

Single-Stage Compressor

1

Reciprocating Two-Stage Compressor 

2

Scroll Two-Stage Compressor

3

TABLE 3: 

Status Code Display

Description

LED1
(Red)

LED2

(Green)

No power to control

OFF

OFF

First-stage compressor operation – not 
applicable to single stage compressor

OFF

ON

Second-stage or full capacity compressor 
operation

ON

ON

Control normal operation – no 
call for compressor

OFF

2 sec ON

2 sec OFF

Control normal operation – call for com-
pressor and ASCD timer (5 min.) is active

OFF

Rapid 

Flash

No fault codes in memory – Initiated 
by LAST ERROR pushbutton

2

2

Fault code memory cleared – Initiated 
by LAST ERROR pushbutton

3

3

TABLE 4: 

X/L Output Categories

Condition Category

X/L

Soft Lockout – Reset with interruption of thermostat 
call following correction of fault condition

2 flashes

Hard Lockout – Reset by cycling power 
to system

3 flashes

Wiring, sensor or control setting related error

4 flashes

Summary of Contents for YZE SERIES

Page 1: ...ractices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installatio...

Page 2: ...topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide an adequate structural support ADD ON...

Page 3: ...a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the out door unit to facilitate proper oi...

Page 4: ...tem from the vapor service port connection After this con nection has cooled remove the nitrogen source from the liquid fit ting service port 7 Replace the Schrader core in the liquid and vapor valves...

Page 5: ...a vertical run the bulb should be located at least 16 inches from any bend and on the tub ing sides opposite the plane of the bend The bulb should be positioned with the bulb tail at the top so that t...

Page 6: ...hat a mini mum air flow of 325 cfm ton be supplied at all times CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly Refer to the Tabular Data...

Page 7: ...operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around 10 F This may vary greatly base...

Page 8: ...ys that are already energized but will not energize any additional relays until the voltage level increases If the voltage drops below approximately 16 VAC the control will imme diately de energize th...

Page 9: ...not be displayed when a fault code is present During the following conditions the control will not energize the X L out put FAULT CODE DISPLAY X L Output The X L terminal of the heat pump control is...

Page 10: ...ored fault codes from the control s memory This practice will enable better troubleshooting and diagnosis of system problems If the stored fault codes are not cleared after the cause of the problem ha...

Page 11: ...be removed and reapplied When the hard lockout condition is reset the control will de energize the LED and X L outputs and respond to thermostat inputs normally Wiring or Setting Related Lockouts The...

Page 12: ...ing cycle The control will initiate a defrost cycle every 6 hours accumulated com pressor run time to recirculate refrigerant lubricants This forced defrost timer will be reset and restarted following...

Page 13: ...es Recycling 24VAC to the control Shorting the TEST input pins If the Y2 LOCK jumper is in the OFF position the control will not imple ment second stage anticipation mode This results in second stage...

Page 14: ...uid line temperature Therefore if the control energizes Y2 OUT because the outdoor ambient temperature is greater than or equal to 50F or because the liquid line temperature exceeds the curve for the...

Page 15: ...ode If the other exit conditions are met while the unit is in defrost mode the control will complete the defrost cycle and then exit the forced second stage feature During defrost operation the contro...

Page 16: ...re is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under som...

Page 17: ...t the control will de energize the compressor outputs and energize W1 OUT and W2 OUT immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The...

Page 18: ...this document for detailed information The Y2 Lock jumper on the control is shown in figures 11 14 The fac tory places the Y2 Lock jumper in the ON position If the jumper is removed the control will...

Page 19: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only...

Page 20: ...404 11 105 412 6 416 9 426 12 431 11 110 441 7 445 9 454 12 458 11 115 471 8 475 10 482 12 487 11 120 503 9 507 10 512 11 516 11 125 536 10 540 10 543 11 546 10 TABLE 15 15Z48HP Subcooling Charging C...

Page 21: ...035 20401 001 Rev A 0904 Unitary Products Group 21 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram...

Page 22: ...035 20401 001 Rev A 0904 22 Unitary Products Group NOTES...

Page 23: ...035 20401 001 Rev A 0904 Unitary Products Group 23...

Page 24: ...ct to change without notice Printed in U S A 035 20401 001 Rev A 0904 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: