background image

035-20401-001 Rev. A (0904)

Unitary Products Group

13

COOLING OPERATION

First-Stage Cooling Operation

During first-stage cooling operation, the control will receive thermostat
signals at the Y1 and O input terminals. The control will energize the M
compressor output terminal. This signal energizes the coil of the com-
pressor contactor causing the compressor to run. The control also
closes the outdoor fan relay delivering power to the ODF terminal caus-
ing the outdoor fan to operate. The control energizes the RV terminal
with 24VAC to switch the reversing valve.

Second Stage Cooling Operation

During second-stage cooling operation, the control will receive thermo-
stat signals from Y1, Y2 and O inputs. The control will energize both the
M and M2 compressor output terminals. The M signal energizes the
compressor contactor causing the compressor to run. The M2 signal
energizes the isolation relay coil which closes the relay’s normally open
contacts. This closure energizes the 24V compressor solenoid causing
the compressor to operate in second stage. During two-stage cooling
operation the control also closes the ODF relay causing the outdoor fan
to operate. The control energizes the RV terminal with 24VAC to switch
the reversing valve. Additionally, the Y2 OUT terminal is energized with
24VAC. This signal can be used to signal the indoor unit to deliver high
air flow.

Two-Stage Cooling Anticipation Mode

The second-stage anticipation mode applies only to cooling operation. It
does not apply to heating operation.

The purpose of this mode is to allow the unit to bypass first stage oper-
ation under very hot conditions when the unit will most likely require
second stage operation anyway.

The factory setting for second-stage cooling anticipation mode is OFF.

If the control receives two consecutive calls for second-stage cooling
(Y1+Y2+O), it shall force second stage compressor operation with the
next call for first stage cooling (Y1+O). The control shall continue to
force second stage cooling operation with thermostat calls for first stage
cooling until one of the following conditions occurs.

A thermostat call for first stage cooling (Y1+O) that has duration
of less than 10 minutes.

Recycling 24VAC to the control

Shorting the TEST input pins.

If the Y2 LOCK jumper is in the OFF position, the control will not imple-
ment second-stage anticipation mode. This results in second-stage
operation only when the room thermostat calls for second-stage cooling
(Y1 + Y2 + 0).

If the jumper is removed, the control will behave as if the jumper is in
the OFF position.

HEATING OPERATION

First-Stage Heating Operation

During first-stage heating operation, the control will receive a thermo-
stat signal at the Y1 input terminal. The control will energize the M com-
pressor output terminal. This signal energizes the coil of the
compressor contactor causing the compressor to run. The control also
closes the outdoor fan relay delivering power to the ODF terminal caus-
ing the outdoor fan to operate. The reversing valve is not energized in
heating mode. 

Second-Stage Heating Operation

During second-stage heating operation, the control will receive a ther-
mostat signal at the Y1 and Y2 input terminals. The control will energize
the M and M2 compressor output terminals. The M signal energizes the
coil of the compressor contactor causing the compressor to run. The
M2 signal energizes the isolation relay coil which closes the relay’s nor-
mally open contacts. This closure energizes the 24V compressor sole-
noid causing the compressor to operate in second-stage. The control
also closes the ODF relay causing the outdoor fan to operate. The Y2
OUT terminal may or may not be energized depending on the HP mode
of operation (conventional vs. hot heat pump).

Conventional Heat Pump Mode

The factory setting of the HOT HEAT PUMP jumper on the control is the
OFF position. In this configuration the heat pump operates in conven-
tional heat pump mode. If the jumper is not in place, the control will act
as if the jumper is in the OFF position.

If the HOT HEAT PUMP jumper is in the OFF position, the control will
energize the Y2 OUT terminal whenever the compressor is running in
second-stage.

The location of the hot heat pump jumper is shown in Figures 11 & 14.

 FIGURE 12: 

Defrost Operation Curves

REGION C

TERMINATE CURVE

INHIBIT CURVE

INITIA

TE CURVE

REGION A

REGION B

REGION D

REGION E

AMBIENT TEMPERATURE

LIQUID LINE (COIL) TEMPERA

TURE

Defrost prevented from starting

No call for defrost

Time Defrost (6 hour) prevented

No call for Defrost

Time Defrost (6 hour) allowed

Call for Defrost

Defrost Terminated

Summary of Contents for YZE SERIES

Page 1: ...ractices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installatio...

Page 2: ...topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide an adequate structural support ADD ON...

Page 3: ...a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the out door unit to facilitate proper oi...

Page 4: ...tem from the vapor service port connection After this con nection has cooled remove the nitrogen source from the liquid fit ting service port 7 Replace the Schrader core in the liquid and vapor valves...

Page 5: ...a vertical run the bulb should be located at least 16 inches from any bend and on the tub ing sides opposite the plane of the bend The bulb should be positioned with the bulb tail at the top so that t...

Page 6: ...hat a mini mum air flow of 325 cfm ton be supplied at all times CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly Refer to the Tabular Data...

Page 7: ...operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around 10 F This may vary greatly base...

Page 8: ...ys that are already energized but will not energize any additional relays until the voltage level increases If the voltage drops below approximately 16 VAC the control will imme diately de energize th...

Page 9: ...not be displayed when a fault code is present During the following conditions the control will not energize the X L out put FAULT CODE DISPLAY X L Output The X L terminal of the heat pump control is...

Page 10: ...ored fault codes from the control s memory This practice will enable better troubleshooting and diagnosis of system problems If the stored fault codes are not cleared after the cause of the problem ha...

Page 11: ...be removed and reapplied When the hard lockout condition is reset the control will de energize the LED and X L outputs and respond to thermostat inputs normally Wiring or Setting Related Lockouts The...

Page 12: ...ing cycle The control will initiate a defrost cycle every 6 hours accumulated com pressor run time to recirculate refrigerant lubricants This forced defrost timer will be reset and restarted following...

Page 13: ...es Recycling 24VAC to the control Shorting the TEST input pins If the Y2 LOCK jumper is in the OFF position the control will not imple ment second stage anticipation mode This results in second stage...

Page 14: ...uid line temperature Therefore if the control energizes Y2 OUT because the outdoor ambient temperature is greater than or equal to 50F or because the liquid line temperature exceeds the curve for the...

Page 15: ...ode If the other exit conditions are met while the unit is in defrost mode the control will complete the defrost cycle and then exit the forced second stage feature During defrost operation the contro...

Page 16: ...re is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under som...

Page 17: ...t the control will de energize the compressor outputs and energize W1 OUT and W2 OUT immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The...

Page 18: ...this document for detailed information The Y2 Lock jumper on the control is shown in figures 11 14 The fac tory places the Y2 Lock jumper in the ON position If the jumper is removed the control will...

Page 19: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only...

Page 20: ...404 11 105 412 6 416 9 426 12 431 11 110 441 7 445 9 454 12 458 11 115 471 8 475 10 482 12 487 11 120 503 9 507 10 512 11 516 11 125 536 10 540 10 543 11 546 10 TABLE 15 15Z48HP Subcooling Charging C...

Page 21: ...035 20401 001 Rev A 0904 Unitary Products Group 21 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram...

Page 22: ...035 20401 001 Rev A 0904 22 Unitary Products Group NOTES...

Page 23: ...035 20401 001 Rev A 0904 Unitary Products Group 23...

Page 24: ...ct to change without notice Printed in U S A 035 20401 001 Rev A 0904 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: