background image

035-20401-001 Rev. A (0904)

Unitary Products Group

19

Low Discharge Line Temperature

The control will begin a sixty-minute timer when either of the following
conditions are met. 

The discharge line temperature has not reached 90F after eight
minutes of accumulated compressor run time.

The discharge temperature has not reached 90F after fifteen min-
utes of accumulated compressor run time following the exit of a
defrost cycle.

If the discharge line temperature has not reached 90F after the sixty-
minute timer has expired, the control will cause a soft lockout condition.
The control will reset the sixty-minute timer upon expiration and when
the compressor starts. The timer is reset when the compressor starts
and is only restarted if one of the two conditions shown above are met.

The low discharge temperature fault indicates that the outdoor coil is
too cold during heating operation. The lockout is intended to prevent
refrigerant flooding back to the compressor.

IMPORTANT: The discharge sensor must be well insulated and
installed properly to prevent nuisance lockouts from occurring.

INDICATIONS OF PROPER OPERATION

Cooling

Cooling operation is the same as any conventional air conditioning unit.

1.

The outdoor fan should be running, with warm air being dis-
charged from the top of the unit.

2.

The indoor blower (furnace or air handler) will be operating, dis-
charging cool air from the ducts. Coils or other parts in the air cir-
cuit should be cleaned as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment, or other suitable
means.

3.

The vapor line at the outdoor unit will feel cool to the touch.

4.

The liquid line at the outdoor unit will feel warm to the touch.

Heating

Indications of proper Heating operation is as follows:

1.

The outdoor fan should be running, with cool air being discharged
from the top of the unit.

2.

The indoor blower (furnace or air handler) will be operating, dis-
charging warm air from the ducts.

3.

The vapor line at the outdoor unit will feel warm to the touch.

4.

The liquid line at the outdoor unit will feel cool to the touch.

SECTION IX: INSTRUCTING THE OWNER

Assist owner with processing warranty cards and/or online registration.
Review Owners Guide and provide a copy to the owner and guidance
on proper operation and maintenance. Instruct the owner or the opera-
tor how to start, stop and adjust temperature setting.

When applicable, instruct the owner that the compressor is equipped
with a crankcase heater to prevent the migration of refrigerant to the
compressor during the “OFF” cycle. The heater is energized only when
the unit is not running. If the main switch is disconnected for long peri-
ods of shut down, do not attempt to start the unit until 8 hours after the
switch has been connected. This will allow sufficient time for all liquid
refrigerant to be driven out of the compressor.

The installer should also instruct the owner on proper operation and
maintenance of all other system components.

MAINTENANCE

1.

Dirt should not be allowed to accumulate on the outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.

2.

The outdoor fan motor is permanently lubricated and does not
require periodic oiling.

3.

If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.

4.

Refer to the furnace or air handler instructions for filter and blower
motor maintenance.

5.

The indoor coil and drain pan should be inspected and cleaned
regularly to prevent odors and assure proper drainage.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DIS-
POSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

TABLE 12: 

R-410A Saturation Properties

TEMP. 

°

F

PRESSURE 

PSIG

TEMP. 

°

F

PRESSURE 

PSIG

TEMP. 

°

F

PRESSURE 

PSIG

TEMP. 

°

F

PRESSURE 

PSIG

TEMP. 

°

F

PRESSURE 

PSIG

45

129.70

60

169.60

75

217.40

90

274.10

105

340.50

46

132.20

61

172.60

76

220.90

91

278.20

106

345.30

47

134.60

62

175.50

77

224.40

92

282.30

107

350.10

48

137.10

63

178.50

78

228.00

93

286.50

108

355.00

49

139.60

64

181.60

79

231.60

94

290.80

109

360.00

50

142.20

65

184.60

80

235.30

95

295.10

110

365.00

51

144.80

66

187.70

81

239.00

96

299.40

111

370.00

52

147.40

67

190.90

82

242.70

97

303.80

112

375.10

53

150.10

68

194.10

83

246.50

98

308.20

113

380.20

54

152.80

69

197.30

84

250.30

99

312.70

114

385.40

55

155.50

70

200.60

85

254.10

100

317.20

115

390.70

56

158.20

71

203.90

86

258.00

101

321.80

116

396.00

57

161.00

72

207.20

87

262.00

102

326.40

117

401.30

58

163.90

73

210.60

88

266.00

103

331.00

118

406.70

59

166.70

74

214.00

89

270.00

104

335.70

119

412.20

Summary of Contents for YZE SERIES

Page 1: ...ractices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installatio...

Page 2: ...topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide an adequate structural support ADD ON...

Page 3: ...a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the out door unit to facilitate proper oi...

Page 4: ...tem from the vapor service port connection After this con nection has cooled remove the nitrogen source from the liquid fit ting service port 7 Replace the Schrader core in the liquid and vapor valves...

Page 5: ...a vertical run the bulb should be located at least 16 inches from any bend and on the tub ing sides opposite the plane of the bend The bulb should be positioned with the bulb tail at the top so that t...

Page 6: ...hat a mini mum air flow of 325 cfm ton be supplied at all times CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly Refer to the Tabular Data...

Page 7: ...operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around 10 F This may vary greatly base...

Page 8: ...ys that are already energized but will not energize any additional relays until the voltage level increases If the voltage drops below approximately 16 VAC the control will imme diately de energize th...

Page 9: ...not be displayed when a fault code is present During the following conditions the control will not energize the X L out put FAULT CODE DISPLAY X L Output The X L terminal of the heat pump control is...

Page 10: ...ored fault codes from the control s memory This practice will enable better troubleshooting and diagnosis of system problems If the stored fault codes are not cleared after the cause of the problem ha...

Page 11: ...be removed and reapplied When the hard lockout condition is reset the control will de energize the LED and X L outputs and respond to thermostat inputs normally Wiring or Setting Related Lockouts The...

Page 12: ...ing cycle The control will initiate a defrost cycle every 6 hours accumulated com pressor run time to recirculate refrigerant lubricants This forced defrost timer will be reset and restarted following...

Page 13: ...es Recycling 24VAC to the control Shorting the TEST input pins If the Y2 LOCK jumper is in the OFF position the control will not imple ment second stage anticipation mode This results in second stage...

Page 14: ...uid line temperature Therefore if the control energizes Y2 OUT because the outdoor ambient temperature is greater than or equal to 50F or because the liquid line temperature exceeds the curve for the...

Page 15: ...ode If the other exit conditions are met while the unit is in defrost mode the control will complete the defrost cycle and then exit the forced second stage feature During defrost operation the contro...

Page 16: ...re is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under som...

Page 17: ...t the control will de energize the compressor outputs and energize W1 OUT and W2 OUT immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The...

Page 18: ...this document for detailed information The Y2 Lock jumper on the control is shown in figures 11 14 The fac tory places the Y2 Lock jumper in the ON position If the jumper is removed the control will...

Page 19: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only...

Page 20: ...404 11 105 412 6 416 9 426 12 431 11 110 441 7 445 9 454 12 458 11 115 471 8 475 10 482 12 487 11 120 503 9 507 10 512 11 516 11 125 536 10 540 10 543 11 546 10 TABLE 15 15Z48HP Subcooling Charging C...

Page 21: ...035 20401 001 Rev A 0904 Unitary Products Group 21 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram...

Page 22: ...035 20401 001 Rev A 0904 22 Unitary Products Group NOTES...

Page 23: ...035 20401 001 Rev A 0904 Unitary Products Group 23...

Page 24: ...ct to change without notice Printed in U S A 035 20401 001 Rev A 0904 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: