8. Press the SYSTEM SWITCHES key, and turn
on the System SWITCH. There may be a few
seconds delay before the compressor starts be-
cause of the anti-recycle timer. Be ready, when
the compressor starts, to switch the UNIT switch
to the OFF position immediately, if any unusual
noises or other adverse conditions develop. ......
9. When the compressor starts, press the relevant
System Pressures key to verify that oil differen-
tial pressure develops immediately. If oil pres-
sure does not develop, the automatic controls
will shut down the compressor. Under no cir-
cumstances should a restart attempt be made
on a compressor, which does not develop oil
pressure immediately. Switch the UNIT switch
to the OFF position.. ...........................................
10. Adjust condenser refrigerant liquid level setpoint
to a value that covers the subcooler
top and pro-
vides proper evaporator performance with the
chiller running steady. ........................................
11. After the chiller is at full load at Design Leaving
Chilled Liquid Temperature, capture the operat-
ing data to print or save to text file. ....................