JOHNSON CONTROLS
121
SECTION 6 - OPERATION
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
6
To view the schedule without making a change, press
the SCHEDULE key until the day appears. The ▲ key
will scroll to the previous screen.
If the schedule is changed for Monday,
all other days will change to the Monday
schedule, which means if the Monday
times are not applicable for the whole
week, then the exceptional days need to
be reprogrammed to the desired schedule.
SCHEDULE
UNIT OPERATING
HOL START = 00:00 AM STOP = 00:00 PM
To program the chiller for 24-hour operation, program
the start and stop times of each day at 00:00.
After the SUN (Sunday) schedule appears on the dis-
play,, a ▲ key will display the holiday schedule, which
is a two-part display. The first display reads:
SCHEDULE
UNIT OPERATING
S M T W T F S HOLIDAY NOTED BY *
Set the holiday times using the same procedure de-
scribed for the days of the week. Press the
key after
setting the HOL START and STOP times to save the
change in memory. Press the SCHEDULE key a sec-
ond time to show the individual days:
The line below the empty space is the cursor, which
will move to the next or previous empty space when
the ◄ or ► key is pressed.
To set a day for the HOLIDAY NOTED BY:
1. Move the cursor to the space following the day of
the week.
2. Press the asterisk (*) key, and an * will appear in
the space signifying that day as a holiday.
The holiday schedule must be programmed weekly. If
there is no holiday, use the * key to delete the *. Use
the
key to accept the holiday schedule for the entire
week.
The HOLIDAY SCHEDULE is tempo-
rary. Once the schedule is executed, the
selected holidays will be cleared from
memory for the following week.
Summary of Contents for YVWA