8
OPERATING RANGE
Voltage Range
The maximum fluctuation range of supply voltage is ±10%
Three-phase electric phase unbalance rate should be less than 2%.
Temperature range
TABLE 1
-Temperature range(YVAG012~040)
Project
012~018
020~040
Relative humidity
<90%,
No lon
<90%,
No lon
Wire controller using the environment
temperature
-10℃~55℃
-10℃~55℃
The unit running environment
temperature range
Cooling
-5℃~48℃
Heating
-20℃~43℃
Cooling
-5℃~48℃
Heating
-25℃~43℃
Chilled water temperature range
(
Leaving water temperature
)
Cooling
5℃~25℃
Heating
30℃~52℃
Cooling
5℃~25℃
Heating
30℃~58℃
Chilled water temperature range
(
Enter water temperature
)
Cooling
10℃~30℃
Heating
25℃~47℃
Cooling
10℃~30℃
Heating
25℃~53℃
Please note that
The return water temperature control is default by the unit controller, and return water temperature
control is recommended.
The above data are obtained in the laboratory, the practical use there will be deviation affected by
the installation position and so on.
For applications with temperature below -25
℃
, please consult YORK company.
Applicable Medium
The standard design applicable medium of the unit is purified water. Please consult YORK Company for special
medium such as glycol antifreeze fluid.
Altitude
No more than 2000m