SECTION 1 – INSTALLATION
INSPECTION – DAMAGE – SHORTAGE
The unit shipment should be checked on arrival to see
that all major pieces, boxes and crates are received.
Each unit should be checked on the trailer when re-
ceived, before unloading, for any visible signs of dam-
age. Any dam age or signs of possible damage must be
reported to the transportation company immediately
for their inspection.
Johnson Controls will not be responsible
for any dam age in shipment or at job site
or loss of parts.
When received at the job site all containers should be
open ed and contents checked against the packing list.
Any ma terial shortage should be reported to Johnon
Controls immediately. (Refer to
Shipping Damage
Claims (Form 50.15‑NM)
.)
DATA PLATE
A unit data plate is mounted on the control center as-
sembly of each unit, giving unit model number; design
working pressure; water passes; refrigerant charge; se-
rial numbers; and motor power characteristics and con-
nection diagrams. Refer to NOMENCLATURE on
4 to verify data plate markings.
LOCATION
The chiller should be located in an indoor location
where temperature ranges from 40°F to 110°F (4°C to
43°C).
The units are furnished with neoprene vibration isola-
tor mounts for basement or ground level installations.
Units may be located on upper floor levels provided
the floor is capable of supporting the total unit operat-
and
Equipment room should be ventilated to allow ad-
equate heat removal. Check ANSI, state, local or other
codes.
FOUNDATION
A level floor, mounting pad or foundation must be pro-
vided by others, capable of supporting the operating
weight of the unit.
CLEARANCE FOR SERVICE REQUIREMENTS
Clearances should be adhered to as follows:
Rear, Ends and Above Unit – 2 Feet / 610 mm
Front of Unit
– 3 Feet / 914 mm
Tube Removal
– See
TABLE 2 -
SERVICE CLEARANCE REQUIREMENTS
SHELL CODES
TUBE REMOVAL
SPACE
ADD – MARINE
WATERBOXES
Ft. - In.
mm
Ft. - In.
mm
TB, TC, TD
10'-1"
3073
2'-2"
660
VB, VC, VD
14'-1"
4293
2'-2"
660
WB, WC, WD
12'-1"
3683
2'-2"
660
XB, XC, XD
16'-1"
4902
2'-2"
660
RIGGING
The complete standard unit is shipped without skids.
(When optional skids are used, it may be necessary to
remove the skids so riggers skates can be used under
the unit end sheets to reduce the overall height.)
Each unit has four lifting holes (two on each end) in
the end sheets which should be used to lift the unit.
Care should be taken at all times during rigging and
handling to avoid damage to the unit and its external
connections. Lift only using holes shown in
.
Do not lift the unit with slings around
motor/compressor assembly or by means
of eyebolts in the tapped holes of the
compressor motor assembly. Do not turn
a unit on its side for rigging. Do not rig
with driveline in a vertical orientation.
If necessary to rig a unit by one end to
permit lifting or dropping through a verti-
cal passageway, such as an elevator shaft,
contact YORK Factory for special rigging
instructions.
The shipping and operating weights are given
in
. Overall dimensions are shown
in
. More detailed dimensions
can be found in Form 160.81-PA1.