COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL
W
RATED
CFM
NET MBH
SEER
EER
TOTAL
SENSIBL
E
1 PH 13 SEER HP WITH MA
YMB01811
MA08B
17
FC/MC18B
600
17.3
12.1
13.00
11.00
YMB02411
MA08B
17
FC/MC24B
800
23.0
16.3
13.00
11.00
MA08B
17
FC/MC30B
800
23.0
16.3
13.00
11.00
YMB03011
MA12B
17
FC/MC35B
1000
28.6
20.3
13.00
11.00
MA12B
17
FC/MC42B
1000
28.6
20.3
13.00
11.00
YMB03611
MA12B
17
FC/MC42B
1200
34.6
25.0
13.00
11.00
MA14D
24
FC/MC48D
1200
35.2
25.5
13.50
11.00
YMB04211
MA16C
21
FC60C
1400
41.5
30.7
13.00
11.00
MA14D
24
FC/MC60D
1400
41.5
30.7
13.00
11.00
YMB04811
MA16C
21
FC60C
1600
47.0
34.2
13.00
11.00
MA20D
24
FC/MC60D
1600
47.0
34.2
13.00
11.00
YMB06011
MA20D
24
FC/MC60D
1800
55.0
37.9
13.00
11.00
MA20D
24
MC61D
1800
55.5
38.3
13.00
11.00
1 PH 13 SEER HP WITH MV - VARIABLE SPEED
YMB01811
MV12B
17
FC/MC18B
600
17.5
12.0
14.00
11.50
YMB02411
MV12B
17
FC/MC24B
800
23.4
16.3
14.00
11.50
MV12B
17
FC/MC30B
800
23.4
16.3
14.00
11.50
YMB03011
MV12B
17
FC/MC35B
1000
29.0
20.1
14.00
11.50
MV12B
17
FC/MC42B
1000
29.0
20.1
14.00
11.50
YMB03611
MV16C
21
FC/MC48C
1200
36.0
25.3
14.00
11.50
MV20D
24
FC/MC48D
1200
36.0
25.3
14.00
11.50
YMB04211
MV16C
21
FC60C
1400
41.0
29.6
13.50
11.00
MV20D
24
FC/MC60D
1400
42.0
30.2
14.00
11.50
YMB04811
MV16C
21
FC60C
1600
46.0
32.7
13.25
11.00
MV20D
24
FC/MC60D
1600
47.0
33.3
13.50
11.00
YMB06011
MV20D
24
FC/MC60D
1800
55.0
37.2
13.25
11.00
MV20D
24
MC61D
1800
55.5
37.6
13.25
11.00
1 PH 13 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED
YMB01811
AV24
17
–
600
17.5
12.0
14.00
11.50
YMB02411
AV24
17
–
800
23.4
16.3
14.00
11.50
YMB03011
AV36
21
–
1000
29.0
20.1
14.00
11.50
YMB03611
AV36
21
–
1200
36.0
25.3
14.00
11.50
YMB04211
AV/SV48
24
–
1400
42.0
30.2
14.00
11.50
AV/SV60
24
–
1400
42.0
30.2
14.00
11.50
F*FV060
24
–
1400
42.0
30.2
14.00
11.50
YMB04811
AV/SV48
24
–
1600
47.0
33.3
13.50
11.00
AV/SV60
24
–
1600
47.0
33.3
13.50
11.00
F*FV060
24
–
1600
47.0
33.3
13.50
11.00
YMB06011
AV/SV60
24
–
1800
55.0
37.2
13.25
11.00
F*FV060
24
–
1800
55.0
37.2
13.00
11.00
1 PH 13 SEER HP WITH AHP / SHP / F*FP
YMB01811
AHP18
17
–
650
17.4
12.7
13.00
11.00
F*FP024
17
–
600
17.3
12.1
13.00
11.00
YMB02411
AHP24
17
–
830
23.0
16.5
13.00
11.00
YMB03011
AHP30
17
–
1015
28.8
20.4
13.00
11.00
F*FP040
17
–
1000
28.6
20.3
13.00
11.00
YMB03611
AHP36
21
–
1200
35.2
25.5
13.50
11.00
AHP42
21
–
1200
35.2
25.5
13.50
11.00
YMB04211
AHP/SHP48
21
–
1400
41.5
30.7
13.00
11.00
AHP/SHP60
24
–
1400
42.0
30.8
14.00
11.50
F*FP045
21
–
1400
41.5
30.7
13.00
11.00
YMB04811
AHP/SHP48
21
–
1675
47.0
35.0
13.00
11.00
AHP/SHP60
24
–
1600
47.0
34.2
13.50
11.00
YMB06011
AHP/SHP60
24
–
1850
55.0
38.7
13.00
11.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8
0
°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1