Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

YMB03011

INDOOR COIL MODEL NO.

AHP30

CONDENSER 

ENTERING AIR 

TEMPERATURE

ID CFM

800

1000

1200

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

26.3

28.5

28.4

31.2

34.1

28.3

29.2

29.4

32.2

35.2

30.3

29.9

30.4

33.1

36.3

S.C.

25.8

23.4

19.9

19.6

15.5

27.8

26.4

22.0

21.7

16.6

29.8

29.5

24.1

23.8

17.7

K.W.

1.5

1.5

1.5

1.5

1.6

1.5

1.5

1.5

1.5

1.6

1.5

1.5

1.5

1.6

1.6

75

T.C.

25.7

27.4

27.5

30.1

33.0

27.4

28.2

28.4

31.0

33.9

29.2

29.1

29.3

31.9

34.8

S.C.

25.1

23.0

19.5

19.2

15.1

26.9

25.8

21.6

21.3

16.5

28.7

28.6

23.7

23.3

17.8

K.W.

1.7

1.7

1.7

1.7

1.8

1.7

1.7

1.7

1.7

1.8

1.7

1.7

1.7

1.8

1.8

85

T.C.

25.0

26.4

26.5

29.1

31.8

26.6

27.3

27.4

29.9

32.6

28.1

28.2

28.3

30.7

33.4

S.C.

24.5

22.6

19.1

18.8

14.7

26.1

25.2

21.2

20.8

16.3

27.7

27.8

23.3

22.8

17.9

K.W.

1.9

1.9

1.9

1.9

2.0

1.9

1.9

1.9

1.9

2.0

1.9

1.9

1.9

2.0

2.0

95

T.C.

24.3

25.3

25.6

28.0

30.7

25.7

26.3

26.4

28.8

31.3

27.0

27.3

27.2

29.5

31.9

S.C.

23.8

22.2

18.7

18.4

14.3

25.2

24.6

20.8

20.4

16.1

26.6

27.0

22.9

22.4

18.0

K.W.

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.2

2.1

2.2

2.1

2.2

2.2

105

T.C.

22.9

24.0

24.3

26.7

29.3

24.1

25.1

25.0

27.3

29.9

25.4

26.2

25.8

28.0

30.4

S.C.

22.5

21.7

18.2

17.9

13.8

23.7

23.7

20.3

19.9

15.5

25.0

25.8

22.4

21.8

17.1

K.W.

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.5

115

T.C.

21.6

22.7

22.9

25.3

27.9

22.7

23.9

23.7

25.9

28.5

23.8

25.0

24.4

26.5

29.0

S.C.

21.2

21.2

17.8

17.4

13.4

22.3

22.9

19.9

19.3

14.8

23.5

24.6

22.0

21.2

16.2

K.W.

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

125

T.C.

20.2

21.5

21.6

24.0

26.6

21.2

22.6

22.3

24.5

27.1

22.1

23.8

23.1

25.1

27.6

S.C.

19.9

20.6

17.3

16.9

13.0

20.9

22.1

19.4

18.8

14.1

22.0

23.5

21.5

20.7

15.3

K.W.

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

FC/MC35B

0.99

1.00

1.00

MA12B

FC/MC42B

0.99

1.00

1.00

MV12B

FC/MC35B

1.01

0.99

0.96

MV12B

FC/MC42B

1.01

0.99

0.96

AV36

1.01

0.99

0.96

F*FP040

0.99

1.00

1.00

FC/MC/PC35

0.99

1.00

1.00

HC36

1.00

1.00

1.00

HD36

1.00

1.00

1.00

Variable Speed 
Furnace

Coil

T.C.

S.C.

KW

PV8*B16

FC/MC/PC35B

1.01

1.00

0.96

P(C,V)9*B12

FC/MC/PC35B

1.01

1.00

0.96

PV8*B16

HC36

1.01

1.00

0.96

P(C,V)9*B12

HC36

1.01

1.00

0.96

PV8*A12

HD36

1.01

1.00

0.96

PV8*B16

HD36

1.01

1.00

0.96

PV8*C16

HD36

1.02

1.00

0.96

PV8*C20

HD36

1.02

1.01

0.96

PV9*A12

HD36

1.01

1.00

1.00

P(C,V)9*B12

HD36

1.01

1.00

0.96

P(C,V)9*C16

HD36

1.01

1.00

0.96

P(C,V)9*C20

HD36

1.01

1.00

0.96

Summary of Contents for YMB018 THRU 060

Page 1: ...g high quality appearance A powder paint topcoat is applied over a baked on primer using a galvanized zinc coated steel base material The result is a finish that has been proven in testing to provide...

Page 2: ...23 58 23 58 23 58 Rows Deep 1 1 1 1 1 2 2 Fin Inches 22 22 22 22 22 22 22 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 4 3 4 7 8 7 8 7 8 7 8 1 1...

Page 3: ...0 FC MC PC UC42C2C 0 FC MC PC UC48C2C 0 FC MC PC UC48D2C 0 FC PC UC60C2C 0 0 0 FC MC PC UC60D2C 0 0 0 MC61D2C 0 0 HC18A2A 0 HC30A2A 0 HC36B2A 0 HC42C2C 0 HC60D2C 0 0 0 HD24A2A 0 HD36B2A 0 HD48C2C 0 H...

Page 4: ...0 AHP24B3X 2A 0 AHP30B3X 2A 0 AHP36C3X 2A 0 AHP42C3X 2A 0 AHP SHP48D3X 2C 0 2C 0 AHP SHP60D3X 2C 0 2C 0 2C 0 AV24B3X 2A 0 2A 0 AV36C3X 2A 0 2A 0 AV SV48D3X 2C 0 2C 0 AV SV60D3X 2C 0 2C 0 2C 0 F FP024H...

Page 5: ...1 PH 13 SEER HP WITH AV SV F FV VARIABLE SPEED YMB01811 AV24 17 600 17 5 12 0 14 00 11 50 YMB02411 AV24 17 800 23 4 16 3 14 00 11 50 YMB03011 AV36 21 1000 29 0 20 1 14 00 11 50 YMB03611 AV36 21 1200...

Page 6: ...00 11 00 17 HC36 1000 28 8 20 3 13 00 11 00 HD36 1000 28 8 20 3 13 00 11 00 YMB03611 1000 1400 17 21 FC MC PC UC42 1200 34 6 25 0 13 00 11 00 21 24 FC MC PC UC48 1200 35 2 25 5 13 50 11 00 21 HC42 120...

Page 7: ...14 00 11 50 PV8 A12 HD36 1000 29 0 20 4 14 00 11 50 PV8 B16 HD36 1000 29 2 20 5 14 00 11 50 PV8 C16 HD36 1000 29 4 20 5 14 00 11 50 PV8 C20 HD36 1000 29 4 20 6 14 00 11 50 PV9 A12 HD36 1000 29 0 20 4...

Page 8: ...60 1600 47 0 34 1 13 25 11 00 PV8 C16 HD60 1500 47 0 33 1 13 25 11 00 PV8 C20 HD60 1600 47 0 34 4 13 25 11 00 P C V 9 C16 HD60 1600 47 0 34 4 13 00 11 00 P C V 9 C20 HD60 1600 47 0 34 4 13 25 11 00 P...

Page 9: ...2 30 1 78 8 30 MV12B FC MC30B 23 2 3 38 2 01 14 0 2 30 1 78 8 30 YMB03011 MV12B FC MC35B 29 0 3 58 2 37 17 3 2 30 2 20 8 35 MV12B FC MC42B 29 0 3 58 2 37 17 3 2 28 2 22 8 30 YMB03611 MV16C FC MC48C 3...

Page 10: ...ctric heat operation HEATING PERFORMANCE Air Handlers UNIT MODEL AIR HANDLER COIL1 MODEL ARI HEATING2 47 F 17 F HSPF MBH COP KW MBH COP KW STD HEATING PERFORMANCE Furnace Coils UNIT MODEL COIL1 MODEL...

Page 11: ...8 8 15 PV8 B16 HD36 29 0 3 58 2 37 17 3 2 28 2 22 8 30 PV8 C16 HD36 29 0 3 60 2 36 17 3 2 30 2 20 8 35 PV8 C20 HD36 29 0 3 60 2 36 17 2 2 30 2 19 8 35 PV9 A12 HD36 29 4 3 50 2 46 17 6 2 24 2 30 8 10 P...

Page 12: ...V 9 D20 FC MC PC60D 48 0 3 80 3 70 33 2 2 64 3 68 8 65 PV8 C20 HC60 48 0 3 80 3 70 33 2 2 64 3 68 8 65 P C V 9 C20 HC60 48 0 3 78 3 72 33 2 2 60 3 74 8 60 P C V 9 D20 HC60 48 0 3 80 3 70 33 2 2 64 3...

Page 13: ...in harsh winter weather Room Thermostats A wide selection of matching thermo stats is available to provide features required for any installa tion 2H 1C manual changeover electronic non programmable t...

Page 14: ...W 1 1 1 1 1 1 1 2 1 2 1 1 1 2 1 1 1 2 1 2 1 2 1 2 1 2 1 2 1 2 95 T C 13 6 14 9 15 0 16 8 18 7 15 3 15 8 15 7 17 4 19 5 17 0 16 6 16 4 18 0 20 3 S C 13 7 12 4 10 5 10 6 8 5 15 1 14 4 12 2 12 4 9 6 16 6...

Page 15: ...20 9 23 2 26 1 S C 16 7 16 0 13 5 13 6 11 0 18 1 18 4 15 6 15 7 12 4 19 5 20 7 17 6 17 8 13 9 K W 1 7 1 7 1 7 1 8 1 8 1 7 1 7 1 7 1 8 1 8 1 7 1 7 1 7 1 8 1 8 105 T C 16 5 18 0 18 1 20 1 22 5 17 9 19 0...

Page 16: ...8 22 2 18 7 18 4 14 3 25 2 24 6 20 8 20 4 16 1 26 6 27 0 22 9 22 4 18 0 K W 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 2 1 2 2 2 1 2 2 2 2 105 T C 22 9 24 0 24 3 26 7 29 3 24 1 25 1 25 0 27 3 29 9 25 4 2...

Page 17: ...4 29 4 30 2 33 4 30 9 32 0 28 8 30 6 34 4 32 6 32 6 28 2 31 0 35 3 S C 28 8 30 4 23 2 21 8 16 2 30 6 31 4 22 9 22 5 17 7 32 3 32 4 22 6 23 3 19 2 K W 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2 9 2...

Page 18: ...8 33 3 33 4 23 9 K W 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 3 105 T C 34 4 37 3 35 7 38 8 39 6 37 0 38 8 36 5 39 4 39 5 39 7 40 3 37 3 40 1 39 5 S C 33 6 33 4 28 0 27 8 20 7 35 1 35...

Page 19: ...2 41 6 41 8 34 9 34 9 25 3 K W 3 5 3 5 3 5 3 5 3 6 3 5 3 5 3 5 3 5 3 6 3 5 3 5 3 5 3 5 3 6 105 T C 37 2 39 5 37 7 42 4 44 4 39 4 40 5 38 5 43 1 45 1 41 6 41 5 39 4 43 8 45 7 S C 36 5 36 2 30 5 30 0 2...

Page 20: ...45 1 43 9 36 0 36 1 26 6 47 1 46 8 38 7 38 7 28 5 49 0 49 6 41 3 41 2 30 4 K W 4 2 4 3 4 3 4 3 4 4 4 2 4 3 4 3 4 3 4 4 4 2 4 3 4 3 4 3 4 4 105 T C 46 9 47 7 44 9 51 1 52 9 49 0 49 3 46 2 52 3 54 3 51...

Page 21: ...3 3 80 14 7 1 6 2 6 15 3 1 6 2 8 16 0 1 6 3 0 30 60 12 0 1 5 2 3 12 5 1 5 2 4 13 1 1 5 2 5 70 12 5 1 4 2 6 12 9 1 4 2 7 13 2 1 4 2 7 80 13 1 1 3 3 0 13 2 1 3 3 0 13 2 1 3 3 0 17 60 9 5 1 4 1 9 10 7 1...

Page 22: ...2 8 80 16 6 2 1 2 1 17 6 1 9 2 3 18 7 1 8 2 5 17 60 14 3 1 5 2 4 14 8 1 4 2 5 15 2 1 4 2 6 70 13 6 1 7 2 1 14 3 1 6 2 2 15 0 1 6 2 3 80 12 9 1 9 1 8 13 8 1 8 1 9 14 7 1 7 2 1 10 60 11 8 1 5 2 1 12 0...

Page 23: ...23 4 2 2 2 6 23 6 2 1 2 7 17 60 18 8 1 7 2 8 18 9 1 8 2 6 19 1 1 8 2 5 70 18 4 2 0 2 4 18 6 2 0 2 4 18 8 1 9 2 3 80 18 0 2 3 2 1 18 3 2 1 2 1 18 6 2 0 2 2 10 60 16 6 1 8 2 4 16 8 1 7 2 4 17 1 1 7 2 4...

Page 24: ...1 2 3 18 4 2 0 2 3 18 7 2 0 2 3 70 17 7 2 3 2 0 18 0 2 3 2 0 18 4 2 2 2 0 80 17 3 2 6 1 8 17 7 2 5 1 8 18 0 2 4 1 8 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil M...

Page 25: ...9 28 8 2 4 2 9 70 28 0 2 8 2 6 28 3 2 7 2 6 28 6 2 6 2 6 80 27 4 3 1 2 3 27 9 3 0 2 3 28 3 2 9 2 4 10 60 26 0 2 3 2 7 26 1 2 4 2 6 26 2 2 5 2 5 70 25 4 2 7 2 4 25 6 2 7 2 4 25 8 2 7 2 3 80 24 9 3 0 2...

Page 26: ...34 9 2 9 3 0 35 3 2 9 2 9 70 31 8 3 3 2 5 32 6 3 2 2 5 33 5 3 2 2 6 80 29 1 3 7 2 0 30 4 3 6 2 1 31 7 3 5 2 3 10 60 32 3 2 9 2 8 32 4 2 8 2 8 32 5 2 8 2 8 70 30 3 3 2 2 4 30 5 3 1 2 4 30 6 3 0 2 4 80...

Page 27: ...7 45 8 4 8 2 8 45 9 4 6 2 9 17 60 38 3 3 8 2 9 40 1 3 6 3 2 41 9 3 5 3 5 70 36 8 4 0 2 7 38 4 4 0 2 8 40 0 3 9 3 0 80 35 3 4 3 2 4 36 7 4 3 2 5 38 1 4 4 2 6 10 60 33 1 3 4 2 9 34 5 3 5 2 9 36 0 3 6 2...