Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YMB06011
INDOOR COIL MODEL NO.
FC/MC/PC60
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1600
1800
2000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
75.6
4.6
4.8
76.1
4.4
5.1
76.6
4.2
5.3
70
72.9
5.1
4.2
73.4
4.9
4.4
73.8
4.6
4.7
80
70.2
5.6
3.7
70.6
5.3
3.9
71.0
5.1
4.1
47
60
63.8
4.3
4.4
64.2
4.1
4.6
64.7
3.9
4.8
70
61.4
4.8
3.8
61.8
4.6
4.0
62.2
4.4
4.2
80
59.0
5.3
3.3
59.3
5.0
3.4
59.6
4.8
3.6
40
60
53.1
4.0
3.9
53.2
4.2
3.7
53.3
4.3
3.6
70
48.9
4.4
3.3
49.3
4.6
3.1
49.6
4.8
3.0
80
44.7
4.7
2.7
45.4
5.0
2.7
46.0
5.2
2.6
30
60
47.5
4.1
3.4
48.8
3.9
3.6
50.2
3.7
3.9
70
46.6
4.5
3.0
47.3
4.4
3.2
48.1
4.2
3.4
80
45.7
4.9
2.7
45.8
4.8
2.8
45.9
4.6
2.9
17
60
38.3
3.8
2.9
40.1
3.6
3.2
41.9
3.5
3.5
70
36.8
4.0
2.7
38.4
4.0
2.8
40.0
3.9
3.0
80
35.3
4.3
2.4
36.7
4.3
2.5
38.1
4.4
2.6
10
60
33.1
3.4
2.9
34.5
3.5
2.9
36.0
3.6
2.9
70
33.2
3.9
2.5
34.0
3.9
2.5
34.7
3.9
2.6
80
33.4
4.4
2.2
33.4
4.3
2.2
33.4
4.3
2.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MA20D
FC/MC60D
1.00
1.00
1.00
MA20D
MC61D
1.00
1.00
1.00
MV20D
FC/MC60D
1.00
1.02
0.98
MV20D
MC61D
1.00
1.02
0.98
AV/SV60
–
1.00
1.02
0.98
F*FV060
–
1.00
1.02
0.98
AHP/SHP60
–
1.00
1.01
0.99
–
HC60
1.00
1.00
1.00
–
HD60
1.00
1.00
1.00
–
MC61
1.00
1.00
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*D20
FC/MC/PC60D
1.00
1.02
0.98
PV8*C20
FC/PC60C
1.00
1.01
0.99
P(C,V)9*C20
FC/PC60C
1.00
1.01
0.99
PV8*C20
HC60
1.00
1.01
0.99
P(C,V)9*D20
HC60
1.00
1.02
0.98
PV8*C20
HD60
1.00
1.01
0.99
P(C,V)9*C20
HD60
1.00
1.01
0.99
P(C,V)9*D20
HD60
1.00
1.02
0.98
PV8*C20
MC61D
1.00
1.01
0.99
P(C,V)9*C20
MC61D
1.00
1.01
0.99
P(C,V)9*D20
MC61D
1.00
1.02
0.98