![York YMAA 0045 Installation Manual Download Page 41](http://html1.mh-extra.com/html/york/ymaa-0045/ymaa-0045_installation-manual_4255008041.webp)
41
JOHNSON CONTROLS
FORM NO.: 6U6K-B01E-NB-EN
SECTION 4 – INSTALLATION
CONTROL WIRING
Communication Wiring – Optiview LT
Communication Wiring – Wire Controller
FIGURE 22 –
OPTIVIEW LT COMMUNICATION WIRING
FIGURE 23 –
WIRE CONTROLLER COMMUNICATION WIRING
Note
Optiview LT can be rewired to CON203 if wire controller is connected.
TABLE 3 –
COMMUNICATION CABLE REQUIREMENT
TOTAL LENGTH
L
﹤
100 m
100 m
﹤
L
﹤
500 m
L
﹥
500 m
CABLE TYPE
RVVPS 2×0.75mm
2
RVVPS 2×1.0mm
2
CONTACT JCI SERVICE
L=L1+L2+L3+…+Ln (n=32 or n=16, unit: m)
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz