The condensers should be covered to protect the coils and
fins from potential damage and corrosion, particularly where
building work is in progress.
•
The unit should be stored in a location where there is minimal
activity in order to limit the risk of accidental physical damage.
•
To prevent inadvertent operation of the pressure relief devices
the unit must not be steam cleaned.
•
It is recommended that the unit is periodically inspected
during storage.
OPERATING AND STORAGE CONDITIONS
Standard leaving chilled water temp. (Comfort chiller): 5~20°C
Standard leaving chilled water temp. (Brine chiller): -8~20°C
Standard ambient at cooling mode: -17.8~48°C
Standard leaving hot water temp.: 25~55°C
Ambient temp. at heating mode: -15~25°C
Unit storage ambient temp.: -20~55°C
INSPECTION
Remove any transit packing and inspect the unit to ensure that
all components have been delivered and that no damage has
occurred during transit. If any damage is evident, it should
be noted on the carrier’s freight bill and a claim entered in
accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local
Johnson Controls representative.
MOVING THE UNIT BY FORKLIFT TRUCKS
For models of YMAA/YMPA 0045-0130, with or without
hydro kits, it is recommended that the units are moved by
forklift trucks for transit transfer. A wooden pallet is added for
forklift use before shipment.
For models of YMAA/YMPA 0160-0260, forklift truck for
moving the unit is NOT recommended.
LIFTING THE UNIT
Units are provided with lifting holes in the base frame which
accept the accessory lifting lug set as shown in the figure below.
Units are lifted with a spreader bar or frame of sufficient width
to prevent damage to the unit from the lifting chains. The lugs
should be inserted into the respective holes in the base frame
and turned so that the spring loaded pin engages into the hole
and the flanges on the lug lock behind the hole. The lugs should
be attached to the cables/chains using shackles or safety hooks.
DO NOT use the "dragging plates" as lifting lugs when lifting
the units. Please refer to "Lifting Instructions" on each unit
before you lift units.
For models of YMAA/YMPA 0045-0130, the rigging plates
are used for site lifting after being mounted on unit. Two of the
plates must be mounted on Hydro Kit if selected. See figure 14.
FIGURE 12 –
MOVING BG BY FORKLIFT TRUCKS
FIGURE 13 –
LIFTING LUGS
SECTION 3 – HANDLING AND STORAGE
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz