FORM NO.:6U6K-B01E-NB-EN
JOHNSON CONTROLS
120
SECTION 10 – SERVICE AND TROUBLESHOOTING
SERVICE MODE
Service Mode is a mode that allows the user to enable or
disable all of the outputs on the unit, change configuration setup
parameters and view all the inputs.
Refer to Section 7, the HMI operating instructions to view the
following inputs and outputs.
ANALOG AND DIGITAL INPUTS
Table 39
is a quick reference list providing the description of
the inputs. All input connections pertain to the connections at
the microboard.
TABLE 39 –
INPUTS DEFINITIONS
Notes
①
.Only applicable for first unit in modular applications;
②
.N: Not applicable.
③
.Large models (160 to 260 kW) are regarded as two units combined: 160/200 kW: 3 (2+1) systems, 230/260 kW: 4 (2+2) systems.
Port
Definition
Heat
Pump
Coolin
g Only
Heat
Pump
Coolin
g Only
Heat
Pump
Coolin
g Only
ANALOG INPUTS
AI1
System return liquid temperature
Y
Y
Y
Y
Y
Y
AI2
Ambient temperature
Y
Y
Y
Y
Y
Y
AI3
SYS1 fin temperature
Y
Y
Y
Y
Y
Y
AI4
SYS2 fin temperature
N
②
N
Y
Y
Y
Y
AI5
Unit leaving liquid temperature
Y
Y
Y
Y
Y
Y
AI6
System leaving liquid temperature
Y
Y
Y
Y
Y
Y
AI7
SYS1 suction temperature
Y
Y
Y
Y
Y
Y
AI8
SYS2 suction temperature
N
N
Y
Y
Y
Y
AI9
SYS1 Compressor discharge temperature 1
Y
Y
Y
Y
Y
Y
AI10
SYS1 Compressor discharge temperature 2
Y
Y
N
N
Y
Y
AI11
SYS2 Compressor discharge temperature 1
N
N
Y
Y
Y
Y
AI12
SYS2 Compressor discharge temperature 2
N
N
Y
Y
Y
Y
AI20
SYS1 low pressure transducer
Y
Y
Y
Y
Y
Y
AI21
SYS2 low pressure transducer
N
N
Y
Y
Y
Y
AI22
SYS1 high pressure transducer
Y
Y
Y
Y
Y
Y
AI23
SYS2 high pressure transducer
N
N
Y
Y
Y
Y
DIGITAL INPUTS
DI1
SYS1 fan motor overload
Y
Y
Y
Y
Y
Y
DI2
SYS2 fan motor overload
N
N
Y
Y
Y
Y
DI3
SYS1 high pressure and comp. overload
Y
Y
Y
Y
Y
Y
DI4
SYS1 low pressure
Y
Y
Y
Y
Y
Y
DI5
System water flow switch
①
Y
Y
Y
Y
Y
Y
DI6
Cooling/heating switch
①
Y
N
Y
N
Y
N
DI7
Remote ON/OFF
①
Y
Y
Y
Y
Y
Y
DI8
External interlock
①
Y
Y
Y
Y
Y
Y
DI9
Power protection
Y
Y
Y
Y
Y
Y
DI10
SYS2 high pressure and comp. overload
N
N
Y
Y
Y
Y
DI11
SYS2 low pressure
N
N
Y
Y
Y
Y
DI12
Unit water flow switch
Y
Y
Y
Y
Y
Y
0045-0065