45
(1) Parameters to be checked when pressure probes are to be used (low ambient kit accessory) YLCA 5 to 15.
Parameters related to the fans
Display
Description
Level
VS
Unit
Max.
Min.
Value
F01
Fan outlet. 0=absent (function not available);
1=present
F
10 (R/W)
1
0
1
F02
Operating mode:
0 = always ON (function not available)
1 = Parallel with compressor (function not available)
2 = ON/OFF operation (function not available)
3 = Parallel with compressor and speed adjustment.
U
48 (R/W)
3
0
3
F03
Minimum triac voltage
F
49 (R/W)
step
F04
0
50
F04
Maximum triac voltage
F
50 (R/W)
step
100
F03
75
F05
Cold cycle minimum speed temperature
Cool cycle minimum speed pressure (1)
F
24 (R/W)
°C
bar
80
-40
38
22.2
F06
Cool cycle maximum speed temp. differential
Cool cycle maximum speed pressure differential (1)
F
26 (R/W)
°C
bar
50
0
7
3.7
F07
Diferencial temperatura paro del ventilador ciclo frío
Diferencial presión paro del ventilador ciclo frío (1)
F
28 (R/W)
°C
bar
50
0
13
6.5
F08
Cool cycle fan OFF differential
F
30 (R/W)
°C
80
-40
6
F09
Heat cycle minimum speed temperature
F
32 (R/W)
°C
50
0
3
F10
Heat cycle maximum speed differential
F
34 (R/W)
°C
F08
0
6
F11
Fan start-up time
F
51 (R/W)
sec.
120
0
10
F12
Triac impulse duration
F
52 (R/W)
sec.
10
0
2
F13
Fan management in defrost mode.
0 = fan deactivated
1 = fan activated in cool cycle mode (function not available)
2 = fan deactivated until defrost end temperature is reached and
start-up at maximum speed for d16
F
53 (R/W)
2
0
2
F14
Fan operative at start up with high ambient temperature
U
91 (R/W)
sec.
999
0
30
FAN SPEED
F9
CONDENSING
TEMPERATURE
F8
F10
F4
F3
FAN SPEED
F7
EVAPORATION
TEMPERATURE
F5
F6
F4
F3