26
Domestic air conditioner
N
Decreasing at the speed of 1HZ/1
second
P
Decreasing at the speed of 1Hz/10
seconds
Q
Continue to keep the last-time instruction cycle
R
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
5.2.5.3 The control of preventing the overcurrent of the compressor
During the starting process of the compressor, if the curren of the compressor is greater than
17A for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state
appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Then continue to run it only after the the power is off.
During the starting process of the compressor, if the AC current is greater than 12A, the
frequency of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 10A, the
frequency of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 9A, the
frequency of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 8A, the
frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
5.2.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 15A, the
frequency of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the
frequency of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 11A, the
frequency of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 10A, the
frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there’s compensation for AC current protection.
When the outdoor environment temperature is higher than 40
, AC current protection value
decreases by 10AD
When the outdoor environment temperature is higher than 46
,AC current protection value
decreases by 15AD
TC
The compressor stops
Fgh_t1
2
Fgh_t1
65
N Decreasing the frequency rapidly
Fgh_t2
59
Fgh_t2
2
P
Decreasing the frequency slowly
Fgh_t3
55
Fgh_t3
2
Q
Prohibiting increasing the frequency
Fgh_t4
51
Fgh_t4
2
R
Increasing slowly
Fgh_t5
47
Fgh_t5
2
Normal
Functions and control
Summary of Contents for YJHMXH007BARR-FX
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...