Read Before Installation
Maximum Operation Pressure
Applicable Refrigerants
3.4MPa
R22, R407C
4.15MPa
R410A
Use pipes that meet the local standards.
Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R410A is higher than that of the units for use with R22, use pipes with
at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7mm or less may not be used.)
Although it was possible to use type-O for pipes with a size of up to 19.05(3/4") with conventional refrigerants, use type-
1/2H pipes for units that use R410A.(Type-O pipes may be used if the pipe size is 19.05 and the radial thickness is 1.2t.)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase
air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between
1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.
Size(mm)
Radial Thickness(mm)
Size(inch)
Type
Type-O pipes
Type-1/2H or Hpipes
Piping Materials
Types of Copper Pipes (Reference)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
Piping Materials/Radial Thickness
Flare Machining (type-O and OL only)
Flare Machining Dimension(mm)
External dimension of pipes
Size
Dimension A
R410A
R22
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
9.1
13.2
16.6
19.7
24.0
9.0
13.0
16.2
19.4
23.3
Flare Nut
Type-2 flare nuts instead of type-1 nuts are used to increase the strength. The size of some of the flare nuts have also
been changed.
Flare nut dimension(mm)
R410A(Type2)
R22(Type1)
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
6.35
9.52
12.7
15.88
1/4''
3/8''
1/2''
5/8''
0.8t
0.8t
0.8t
1.0t
19.05
3/4''
1.0t
Dimension
A
External dimension of pipes
Size
Dimension B
Dimension B
73
Installation
Summary of Contents for YJHMXH007BARR-FX
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...