25
Domestic air conditioner
When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then
begin initialization.
The scope of refrigerationg valve 90-----480 steps
The scope of heating valve
80-----480 steps
The valves are adjusted according to the degree of superheat
SHa
SHa.
5.2.4
Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then
close the four-way valve.
5.2.5 Protection function
5.2.5.1
TTC high temperature-preventing protection
Once the machine is started, it can run TTC overheating protection of air-blowing, but air-blowing
sensor malfunction must alarm after 4 minutes during which the compressor is started (during the
course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the
mean value of the middle 2 values), take the mean value.
TTC
Abnormal stop
110
Decreasing the frequency rapidly
1HZ/second
100
Decreasing the frequency slowly (1HZ/10seconds)
98
The frequency doesn’t change.
93
Increasing the frequency (1HZ/10second)
90
Increasing the frequency
1HZ/1second
TTC>=110
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to
the indoor, others don’t last.
5.2.5.2
TC high temperature-preventing control of the indoor heating unit
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the
running state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 55
, decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor
heat exchanger is lower than 47
, recover to the normal control.
Functions and control
Summary of Contents for YJHMXH007BARR-FX
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...