Domestic air conditioner
When the outdoor environment temperature is higher than 50
,AC current protection value
decreases by 20AD
5.2.5.5
Antifreezing protection of the indoor heat exchanger
When refrigerating/heating, prevent freezing.
Tpg_indoor
is the minimum value of the effective indoor unit (start it and it is in accord with the
running state).
When Tpg_indoor
ice_temp_1
, the frequency of the compressor decreases at the speed of
1HZ/1second.
When Tpg_indoor
ice_temp_2
, the frequency of the compressor decreases at the speed of
1HZ/10seconds.
When Tpg_indoor begins to rise again, and ice_temp_2
=Tpg_indoor
= ice_temp_3
, the
frequency of thecompressor doesn’t change.
When ice_temp_3 Tpg_indoor ice3
, the frequency of the compressor increases at
the speed of 1HZ/10seconds.
For example, Tpg_indoor<= 0
last for 2 minutes, and then the outdoor unit will stop, and report
underload malfunction, but don’t send malfunction report to the indoor.
The compressor stops for more than 3 minutes, Tpg_indoor> ice2
, the compressor
recovers.
5.2.5.6
The frequency limitation of modification rate
In the field which is controlled by high frequency, if the modification rate is not high enough,
the control-driven chip will enter into weak magnetic control, this will help to relieve the problem
of modification rate. If during the course of weak magnetic control, the modification rate is still not
high enough, enter into the control of decreasing frequency until the alarm of modification rate is
relieved.
5.2.5.7
Temperature protection of the outdoor refrigerating coil
When the defrosting temperature and the sensor’s temperature are higher than 65
, the
frequency of the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to
the lowest frequency. When the temperatures are lower than 65
and higher than 60
, keep
the frequency of the compressor. When the temperatures are lower than 60
, relieve the
defrosting temperature protection.
5.2.5.8
Malfunction display and malfunction handling
a)
For the complete appliance’s malfunctions
Annex 2
If there’s malfunction with the outdoor unit, the light of the outdoor unit will flash and its frequency
is 1HZ, the number of times is according to the table, when a round of flashing is finished, the
11
//ice5
9
ce3
Increasing slowly
8
//ice2
Keeping the frequency
ice_temp_3
6
6
ice_temp_2
5
Decreasing slowly
ice_temp_1
3
Decreasing rapidly
ice_temp_1
0
Stop
Functions and control
Summary of Contents for YJHMXH007BARR-FX
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...