SECTION 6 – OPERATION
OPERATION SWITCH
In this screen section, choices can be made about the
mode of operation for the various devices. Use the but-
tons to make your choice. The choices are:
Forced Dilution:
indicates whether forced dilution is
ON or OFF.
Refrigerant Pump:
indicates whether the refrigerant
pump is operating automatically (Auto mode) or is
stopped (Stop mode)
Purge Mode:
The
Auto
and
Manual
buttons control
the purge operation. The lit button indicates if the purge
mode is Automatic or Manual.
Manual Purge:
The
ON
and
OFF
buttons control the
manual purge operation. The lit button tells you if the
manual purge operation is running or not. If you press
the Purge Mode
Auto
button, the purge is done auto-
matically. If you press the Purge Mode
Manual
button,
the purge starts when you press the Manual Purge
ON
button. The purge stops when you press the Manual
Purge
OFF
button.
Any of the above may be changed.
SELECT UNIT
SI unit: It is to select the metric unit display.
US unit: It is to select the imperial unit display.
SELECT LANGUAGE
Press the button to choose the language to be shown in
the Control Center. Various languages (Japanese, Eng-
lish, Chinese, Chinese Simplified, German, Turkish,
and Swedish) are available.
SAFETY SWITCHES
If any problems occur, the following safety switches
stop the absorption chiller safely.