JOHNSON CONTROLS
135
SECTION 9 - DECOMMISSIONING, DISMANTLING, AND DISPOSAL
FORM 155.35-ICOM2.EN.CE/GB (1018)
DATE: 10/30/2018
9
JOHNSON CONTROLS
9
FORM 155.31-CL1
ISSUE DATE: 11/20/2017
PURGE AMOUNT DATA SHEET (1/1)
User:
Model: YHAU
MFG. No.:
User's machine code:
Measured Date:
Measured by:
Purge Amount from Purge Tank
Flame Reaction Test
Standard: 4.0 cc per min. or smaller
Reaction ( Strong / Weak / None )
Amount of Gas (P) cc/min
Purge Amount from Purge Tank
Elapsed time
1 hour
Consumed time for measurement (m)
min.
Total gas amount (a)
cc
Actual gas amount (b)
cc
(b) = (a) - (P) x (m)
Purge Amount from Absorber
Standard: 4.0 cc/min. or smaller
Elapsed time (T)
min.
1
2
3
5
10
15
20
30
Total gas amount (A)
cc
Increased gas amount (B)
cc
Actual gas amount (C)
cc per
min.
(B) = (A) - previous(A)
(B) - (P) X { (T) - previous (T) }
(C) =
(T) - previous (T)