AFFINITY LOW SILL SERIES INSTALLATION MANUAL
Wiring Schematics cont.
ABC - with ECM Motor and Electronic Stat - 208-230-265/60/1
Handi - Box
Ground
Lug
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
24
V
Tr
an
sf
or
m
er
02/12/18
NOTE 1
Black
Yellow
Black/White
Red 208V
Blue 230V/265V
CFM
P13
P4
SW1
P5
JW
2
P9
LO
O/B
Y2
W
DH
P8
P7
RS485 NET
RS485 NET
P6
RS485 EXP
P3
SW2
On
Future Use
L Output Type
CC – Dual/Single
Acc – Dip 5
Acc – Dip 4
RV – B/O
FP2 – 15
°F/30°F
FP1 – 15
°F/30°F
Com1
LED5
Com2
LED5
Test Mode
F1-3A
P1
C
PWM
1
2
3
4
5
6
7
8
ALM
ALG
ACC COM
ACC NO
ACC NC
R
C
G
Y1
EH2
C
EH1
C
CO
C R
-
+
C R
-
+
Off
Fault
LED1
R
Status
LED3
Config
LED2
CC2
CC
F
C
R
F FG CC CCGCC2
HI
CC2
LO
CC2
G
REVREV FP1 FP1 FP2 FP2 LPS LPSHPSHPS
Aurora Base Control
(ABC)
K1
-R
V R
ela
y
K2-
CC Re
lay
K3-
CC
2 Rel
ay
K4
-Fan R
ela
y
K5-Alarm
Relay
K6-Acc
Relay
F
R
C
CC
G
Y1
C
R
ES
LS
P2
EH1
Y
G
G
G
47
0
470
Resistor
Orange (
01
)
Orange (
02
)
RV
HP
LP
T
FD
RV
Blue (
07
)
Blue (
08
)
Bl
ac
k (
09
)
Bl
ac
k (
10
)
Ye
llo
w
Ye
llo
w
Condensate
Brown (23)
G
reen
CC
Viol
et
(1
4)
Bl
ac
k (
15
)
Notes:
1 – Swap blue and red leads f or 208V operation.
2 – Use ALG Out put for 24V lockout.
3 – Factory wired. Refer to blower t able set tings.
Slow Flash
Fast Flash
Flash Code
Status LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Status LED (LED1, Green)
Normal Mode
Control is Non-Functional
Test Mode
Lockout Active
Dehumidification Mode
Reserved
Reserved
Load Shed
ESD
1 second on and 1 second off
Random Start Delay
Fast Flash
OFF
ON
Slow Flash
Fast Flash
Flash Code 2
Flash Code 3
Flash Code 6
Flash Code 4
Flash Code 5
Aurora LED Flash Codes
100 milliseconds on and 100 milliseconds off
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Reserved
Flash Code 7
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Fast Flash
Fast Flash
No Software Overide
Flash ECM Setting
DIP Switch Overide
Slow Flash
Normal Mode
Input Fault Lockout
High Pressure Lockout
Low Pressure Lockout
Low Water Coil Limit Lockout - FP1
Low Air Coil Limit Lockout - FP2
Reserved
Condensate Overflow Lockout
Over/Under Voltage Shutdown
Reserved
Reserved
Air/Water Coil Limit Sensor Error
Flash Code 1
OFF
Flash Code 2
Flash Code 3
Flash Code 4
Flash Code 5
Flash Code 8
Flash Code 6
Flash Code 7
Flash Code 9
Flash Code 10
Flash Code 11
ECM Configu re Mod e
Fast Flash
Reset Configure Mode
Off
Accessory Relay
Cycle with Blower
Cycle with Compressor
Water Valve Slow Open
Outdoor Air Damper
SW2-4 SW2-5
On
On
Off
Off
On
Off
Off
On
Operation
Event
Normal Mode
Test Mode
Random Start Delay
Compressor On Delay
Compressor Minimum On Time
Compressor Short Cycle Delay
Blower Off Delay
Fault Recognition Delay – High Pressure
Start-Up Bypass – Low Pressure
Fault Recognition Delay – Low Pressure
Start-Up Bypass – Low Water/Air Coil Limit
Fault Recognition Delay – Low Water/Air Coil Limit
Fault Recognition Delay – Condensate Overflow
Thermostat Call Recognition Time
Auxiliary Heat Staging Delay
Emergency Heat Staging Delay
Less than 1 second
5 to 80 seconds
1 second
5 seconds
< 1 second
30 seconds
2 seconds
Less than 1 second
2 minutes
5 seconds
4 minutes
15 seconds
2 minutes
2 minutes
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
2 seconds
2 seconds
5 minutes
2 minutes
20 seconds
7.5 seconds
Aurora Timing Events
Reheat Delay
30 seconds
30 seconds
Water Valve Slow Open Delay
90 seconds
90 seconds
RB
Wh
ite
(1
2)
Bl
ac
k (
13
)
Ye
llo
w
Re
d
Re
d
24V Emergency
Shutdown
ES
ES
No
te 3