JOHNSON CONTROLS
280
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
LD10605
SYSTEM
SWITCHES
KEY
SYSTEM SWITCHES KEY
System Switches Key Operation
The SYSTEM SWITCHES key allows the operator
to turn individual systems ON and OFF. Safety lock-
outs are also reset by selecting the respective system
switch RESET. When the SYSTEM SWITCHES key
is pressed, the following message will appear:
SYSTEM SWITCHES SYS 1 ON / OFF / RESET
◄ ►
=XXXXXXXXXXXXXXX
The display indicates the respective system and it’s on/
off /reset switch status. The
▲▼
(ARROW) keys al-
low scrolling to the next and previous system switch
(System 1, 2, 3, or 4).
SYSTEM SWITCHES SYS 2 ON / OFF / RESET
◄ ►
=XXXXXXXXXXXXXXX
SYSTEM SWITCHES SYS 3 ON / OFF / RESET
◄ ►
=XXXXXXXXXXXXXXX
SYSTEM SWITCHES SYS 4 ON / OFF / RESET
◄ ►
=XXXXXXXXXXXXXXX
The
◄
(LEFT ARROW) or
►
(RIGHT ARROW)
keys allow scrolling through the choices of:
• SYSTEM OFF (default)
• SYSTEM ON
• RESET (LOCKOUT)
The switch selection is accepted into memory by press-
ing the
(ENTER) key.
When the “RESET” selection is made and accepted, it
will not change the position of the switch (either ON
or OFF).
Whenever possible, except in emergen-
cies, always use the associated system
switch to turn off a compressor, which
allows the compressors to go through
a controlled shutdown. Avoid using the
"UNIT" switch to turn off the compres
-
sors.
Summary of Contents for YCIV Series
Page 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...