SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
The values displayed under each of the key presses
may be changed by keying in new values and pressing
the
(ENTER) key to store the new value into mem-
ory. Where more than one value may be keyed in on a
display, a portion of the data that does not need updat-
ing may be skipped by pressing the
(ENTER) key.
The
(ENTER) key must also be pressed after the
last value in the display to store the data into memory.
TABLE 20 -
SETPOINT LIMITS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Leaving Chilled Liquid Setpoint
Water Cooling
40.0°F
60.0°F
44.0°F
4.4°C
15.6°C
6.7°C
Glycol Cooling
15.0°F
70.0°F
44.0°F
-9.4°C
15.6°C
6.7°C
Leaving Chilled Liquid Control Range
-
1.5°F
2.5°F
2.0°F
0.8°C
1.4°C
1.1°C
Max. Remote Temperature Reset
-
2°F
40°F
20°F
1°C
22°C
11°C
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values allowed
under the SETPOINTS key are provided in
Summary of Contents for YCIV Series
Page 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...