SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
Unit Data
Evaporator Leaving and Return Chilled Liquid
Temps
This message indicates the leaving and entering chilled
liquid temperatures at the time of the fault.
Ambient Air Temperature
UNIT
OUTSIDE AMBIENT AIR TEMP = XXX.X °F
This message indicates the ambient air temperature at
the time of the fault.
Load / Unload Timers
UNIT LOAD TIMER = XXX SEC
UNLOAD TIMER = XXX SEC
This message indicates remaining time on the load and
unload timers at the time of the fault.
Chilled Liquid Temperature Error and Rate of
Change
UNIT TEMP ERROR = XXX.X °F
RATE = XXX.X °F/M
This message indicates the temperature error between
the actual and the programmed setpoint at the time of
the fault and the rate of temperature change.
Programmed Lead System Selection and
Flow Switch Status
UNIT LEAD SYSTEM NUMBER = X
FLOW SWITCH = XXX
This message indicates the designated lead system at
the time of the fault and whether the flow switch was
ON (Closed) or OFF (Open) at the time of the fault.
Evaporator Pump and Evaporator Heater
Status
UNIT EVAP PUMP RUN = XXX
EVAP HEATER = XXX
This message indicates the status of the evaporator
pump and the evaporator heater at the time of the fault.
XXX indicates ON or OFF.
Active Remote Control Status
UNIT ACTIVE REMOTE CONTR0L = XXXXXX
This message indicates whether the system was operat-
ing under Active Remote Control (RCC, ISN, LOAD,
TEMP, or SOUND) or standard control (NONE) at the
time of the fault.
UNIT SOUND LIMIT LOCAL = XXX %
ISN = XXX REMOTE = XXX %
This message indicates that sound limiting was in ef-
fect, the amount, and whether it was local or remotely
limited.
VSD Data
VSD Actual and Command Frequency
VSD FREQUENCY ACTUAL = XXX.X HZ
COMMAND = XXX.X HZ
This message indicates the VSD actual operating fre-
quency and the command frequency at the time of the
fault. Actual and command may not match due to load/
unload timers, limitation of 1 Hz per load/unload incre-
ment, and to allowable acceleration/deceleration of the
motor.
VSD COMP 1 = XXX AMPS = XXX %FLA
COMP 2 = XXX AMPS
= XXX %FLA
Compressor AMPS and %FLA
The message indicates the compressor %FLA and cur-
rents for systems 1 and 2 at the time of the fault.
COMP 1 = XXX AMPS
= XXX %FLA
COMP 3 = XXX AMPS
= XXX %FLA
COMP 2 = XXX AMPS
= XXX %FLA
COMP 4 = XXX AMPS
= XXX %FLA
These messages indicate the compressor %FLA and
currents for systems 3 and 4 at the time of the fault. For
3 compressor units, the #4 compressor information is
blanked out.
Summary of Contents for YCIV Series
Page 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...